![ZCS TL Series Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/zcs/tl-series/tl-series_user-manual_3222058066.webp)
66 / 74
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 07/06/2019 Rev. 1.1 “User Manual for 20K-33KTL”
ID26
BusOVP
The bus voltage is too
high.
ID26-ID27 are internal faults of the
inverter; turn off the “DC switch”, wait
5 minutes and then turn it back on
again. Check that the fault is no longer
present. If this is not the case, contact
Technical Support.
ID27
VbusUnbalance
The bus voltage is not
balanced.
ID28
DciOCP
The DCI is too high.
Check the configuration of the input
mode (parallel mode / independent
mode) of the inverter, as indicated in
Section 6.3 (C). “6. Input Mode” of this
user manual. If it is not correct,
change it according to Section 6.3 (A)
“10. Configuration of the Input Mode”
of this manual.
If the input mode is correct, turn off
the “DC switch”, wait 5 minutes and
then turn it back on again. Check that
the fault is no longer present. If this is
not the case, contact Technical
Support. If it is not correct, change it
according to Section 6.3 (A) “10.
Configuration of the Input Mode” of
this manual.
ID29
SwOCPInstant
The grid current is
too high.
Internal faults of the inverter; turn off
the “DC switch”, wait 5 minutes and
then turn it back on again. Check that
the fault is no longer present. If this is
not the case, contact Technical
Support.
ID30
SwBOCPInstant
The input current is
too high.
Check whether the input current is
higher than the maximum input
current of the inverter, then check
the input wiring; if both are correct,
contact Technical Support.
ID31-ID48
Reserved
Reserved
Reserved
ID49
ConsistentFault_VGrid
The grid voltage
sampling value
between the master
DSP and slave DSP is
not suitable.
ID49-ID55 are internal faults of the
inverter; turn off the “DC switch”, wait
5 minutes and then turn it back on
again. Check that the fault is no longer
present. If this is not the case, contact
Technical Support.
ID50
ConsistentFault_FGrid
The grid frequency
sampling value
between the master
DSP and slave DSP is
not suitable.
ID51
ConsistentFault_DCI
The current sampling
value of the automatic
differential circuit
breaker between the