Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Manual of 07/06/2019 Rev. 1.1 “User Manual for 20K-33KTL”
Q(v) Setting
Select “23. Set Q(v)” and press “OK” to enter the relative menu, from which you can change the reactive
power according to the grid voltage required by the local regulations. This function may be required by
various regulations for grid-connected inverters. Use the “Up”, “Down” and “OK” keys to set the time delay
expressed in seconds (*.***s) before the changed Q reactive power will intervene.
81.S1 Check
Select “24. 81.S1Check” and press “OK” to enter the relative menu, from which it will be possible to enable
the frequency restriction thresholds required in special cases by local regulations. With the “Up” and “Down”
keys you can set the “1. Enable 81.S1” and “2. Disable 81.S1” option, and select it with the “OK” key. The
display will show “OK” if the setting is successful.
Fast self-test
1)
During normal operation of the inverter, press the “Back” key to enter the main menu.
2)
Press the “OK” key to enter the “Settings” menu.
3)
Press the “Down” key several times until “25. Fast Self-test” is shown on the screen.
4)
Press “OK” to start the self-test.
5)
The self-test will now start automatically; once completed, press “Down” to display the self-test
results, as shown in the figure.