User Manual for HYD 3-6 kw ES Hybrid Inverter - Rev. 1.1 del 13/06/2019
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
↓
Wait
Testing 27.S1...
↓
Wait
Test 27.S1 OK!
↓
Wait
Testing 27.S2...
↓
Wait
Test 27.S2 OK!
↓
Wait
Testing 81>S1...
↓
Wait
Test 81>S1 OK!
↓
Wait
Testing 81>S2…
↓
Wait
Test 81>S2 OK!
↓
Wait
Testing 81<S1...
↓
Wait
Test 81<S1 OK!
↓
Wait
Testing 81<S2...
↓
Wait
Test 81<S2 OK!
↓
Press “OK”
Self-Test OK!
↓
Press “Down”
59.S1 threshold 253V 900ms
↓
Press “Down”
59.S1: 228V 902ms
↓
Press “Down”
59.S2 threshold 264,5V 200ms
↓
Press “Down”
59.S2: 229V 204ms
↓
Press “Down”
27.S1 threshold 195,5V 400ms
↓
Press “Down”