User Manual for HYD 3-6 kw ES Hybrid Inverter - Rev. 1.1 del 13/06/2019
Identificazione: MD-AL-GI-00
Rev. 4.0 del 31.01.18 - Applicazione: GID
Step 3:
Route the battery cables (F) through the cable gland, then connect the battery wires using the OT
terminal (E).
Step 4:
Fasten the waterproof cover using the 4 screws.
4.2.
Photovoltaic connection
Recommended specifications for DC input cables
Cross-sectional area (mm
2
)
Outer diameter of cable (mm
2
)
Range
Recommended value
4.0~6.0
4,0
4.5~7.8
Procedure:
Step 1:
Prepare the positive and negative photovoltaic cables
Figure 8 – Preparing the positive and negative photovoltaic cables
Step 2:
Insert the crimped positive and negative cables into the corresponding photovoltaic connectors
Figure 9 – Preparing the positive and negative photovoltaic connectors
Step 3:
Make sure that the DC voltage of each photovoltaic string is less than 600V DC and that the polarities of