User Manual 3PH HYD5000-HYD20000-ZSS
Rev. 1.1 16/03/2021
Identification: MD-AL-GI-00
Rev. 1. of 16/03/2021 - Application: GID
75/138
05 00
Denmark
33
Ukraine
01
TR322
35 00
Mexico
LV
06 00
Greece
Continent
38
Wide-Range-60Hz
01
island
39
Ireland EN50438
07 00 Netherlands
40
00
Thailand
PEA
08 00
Belgium
01
MEA
09 00
UK
G99
42 00 LV-Range-50Hz
01
G98
44 00
South Africa
10 00
China
46
00
Dubai
DEWG
01
Taiwan
01
DEWG MV
11 00
France
107 00
Croatia
01
FAR Arrete23
108 00
Lithuania
Table 17 - List of country codes
7.2.4.
Setting of input channel
Input Channel Config
Input
Channel1
Bat input 1
Up↑
Down↓
Bat input 2
OK
↓
Not use
Input
Channel2
Bat input 1
Up↑
Down↓
Bat input 2
OK
↓
Not use
Input
Channel3
PV input 1
Up↑
Down↓
PV input 2
OK
↓
Not use
Input
Channel4
PV input 1
Up↑
Down↓
PV input 2
OK
↓
Not used
In the case of a
single Pylontech battery tower
, set the inputs according to the channel
populated:
•
Input channel 1 → BAT input 1 (if the channel populated is no. 1)
•
Input channel 2 → Not Used
In the case of a
single WeCo battery tower
, set the inputs by populating both channels:
•
Input channel 1 → BAT input 1
•
Input channel 2 → BAT input 1