Insulation test
Prior to fitting the charging station to the back plate, an insulation test must
be carried out on all back plates. If this is done while the charging station is
fitted, the overvoltage protection may be triggered and this will cause the
test to fail.
If a PLC communication module is used as a communication solution, this
must be disconnected during the insulation test in order to avoid erroneous
insulation results caused by the phase coupling function of the PLC
communication module.
Do not insert test probes, wires or anything else into the quick-release
connector on the back plate. Voltage tests should be performed directly on
the terminal screws or using a female connector.
7. For å teste installasjonen etter at lokket er skrudd på må du
bruke hunnkoblingen. Dersom du tester rett på bakplaten vil
koblingene bli ødelagt.
230V
1
Remove the adhesive sticker
Remove the adhesive sticker which protects the contact
on the junction box, if applicable.
2
Test the installation
Use the female connection to test the installation before
continuing the fitting of it. If you test directly on the back
plate, the connections will be damaged.
3
Remove the front cover
Remove the front cover using the SmartKey* special tool
supplied with the charging station, and take the front
cover off.
* To remove the front cover on a charging station
mounted on a Zaptec Column, you must use a
SmartKey Column (supplied with the column)
in order to access the charging station.
Install the charging station