32) “INIT VMN HIGH”
Cause:
Before switching the LC on, the software checks the power bridge voltage
without driving it.
The software expects the voltage to be at a “steady state” value.
If it is too high, this alarm occours.
Troubleshooting:
Please check
-
Motor internal connections
-
Motor power cables connections
-
Motor leakage to truck frame
-
If the motor connections are OK, the problem is inside the controller
33) “PUMP VMN NOT OK”
Cause:
Before switching the LC on, the software checks the output voltage on –P
connector, and expects it to be at a “steady state” value (if TRUCK TYPE
options is set to LEVEL=1).
If the voltage is too low, this alarm occours.
Troubleshooting:
Please check
-
The motor connected to –P must be completely still before this alarm
occours. The software waits 30 seconds before showing this alarm. During
this time it shows the “WAIT MOTOR STILL” warning (see in the warnings
chapter)
-
Motor internal connections
-
Motor power cables connections
-
Motor leakage to truck frame
-
If the motor connections are ok, the problem is inside the controller
Содержание ACEX
Страница 27: ...AFCZP0BC COMBIACX ACEX User Manual Page 27 81 8 DRAWINGS 8 1 Mechanical drawing COMBIACX...
Страница 28: ...Page 28 81 AFCZP0BC COMBIACX ACEX User Manual 8 2 Mechanical drawing ACEX...
Страница 29: ...AFCZP0BC COMBIACX ACEX User Manual Page 29 81 8 3 Connection drawing COMBIACX...
Страница 30: ...Page 30 81 AFCZP0BC COMBIACX ACEX User Manual 8 4 Connection drawing ACEX...
Страница 35: ...AFCZP0BC COMBIACX ACEX User Manual Page 35 81 10 3Description of the console menu 10 3 1 COMBIACX ACEX Menu...