to user needs or unlock further enhanced features.
IMPORTANT: Controllers may only allow configuring signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: to set a parameter to 200 it may be needed to set a value of
200 minus 256 = minus 56. In case of a two byte value the same logic applies: Values greater than 32768 may needed to be given
as negative values too.
Watt Meter Report Period (Parameter Number 1, Parameter Size 2)
If the setting is configured for 1hour (set
value =720), the device will report its instant power consumption every 1 hour to Z-Wave Controller. Unit: 5 seconds
Value
Description
1 — 32767
720 * 5s = 3600s = 1 hour (Default 720)
KWH Meter Report Period (Parameter Number 2, Parameter Size 2)
If the setting is configured for 1hour (set
value =6), the device will report its Accumulated Power Consumption (KW/h) every hour to Z-Wave Controller. Unit: 10min
Value
Description
1 — 32767
6 * 10min = 1hour (Default 6)
Threshold of Watt for Load caution (Parameter Number 3, Parameter Size 2)
This is a warning when the
wattage of load over the preset threshold value, if the load wattage exceeds the setting value the device will send a warning alarm
command to the controller.
Value
Description
10 — 3000
wattage threshold value (Default 3000)
Threshold of KWh for Load caution (Parameter Number 4, Parameter Size 2)
This is a warning when the
KWh of load over the preset threshold value, if the Accumulated Power Consumption exceeds the setting value the device will send
a warning alarm command to the controller.
Value
Description
1 — 10000
KWh threshold value (Default 10000)
Behavior on Power Outages (Parameter Number 5, Parameter Size 1)
Value
Description
0
Switch Off
1
last Switch State (Default)
2
Switch On
Disable Switching Funktion (Parameter Number 11, Parameter Size 1)
In case the plug is used for metering
only this parameter prevents from switching off the load accidently. The over load protection remains active even in this state.
Value
Description
0
Disabled
1
Enabled (Default)