Revised 26/05/10
ALLURE ELECTRONIC Install Ops May2010
Page 4 of 23
DIMENSIONS and CLEARANCES
Diagrams on the following pages are not to scale. All measurements are in millimetres.
The Yunca Allure flued gas fire is to be installed with clearances equal to, or greater than, those
recommended on the following pages, and must comply with NZS 5261:2003/AG601
ZERO CLEARANCE FIREBOX
MANTEL
MODEL
F
G
H
J
K
L
X
FLUE DIA
INNER / OUTER
630 *
400
360
295
590
640
730
580
150/200
730
400
360
235
590
670
900
740
150/200
930
400
360
235
590
670 1100
940
200/250
* Production of the 630 model was discontinued in 2010, however the installation,
maintenance and operation information has been retained in this manual for ease of
reference by existing owners.
Also available is a Bottom Fascia Strip for each model. This 85mm high strip is fitted below
a regular three-sided fascia for a “picture frame” look.
CLEARANCES:
Floor protector – 300mm in front of and 100mm from side of firebox opening. 6mm minimum
thickness, using heat resistant materials.
Built in heat cell (zero clearance) requires minimum 25mm from combustibles all around.
Mantel – 300mm above fascia required when the mantel projects no more than 75mm.
Side to wall – 300mm from firebox opening.