sMoke baffles
The smoke baffles are factory installed and must
be checked to see that they have not become
dislodged during shipping. Refer to Fig. 6 for
proper installation and, if necessary to reposition,
proceed as follows:
1. Holding baffle in proper position, tilt rear
up to clear baffle mounting brackets.
2. Push baffle up to top of combustion
chamber above all three brackets, level
off , slide left and lower onto mounting
brackets.
3. Check to see that all three brackets are
engaged.
4. Repeat with second baffle, making sure baffles interlock as shown in Fig. 6. When properly installed, baffles will not move
more than 1/4" in any direction. Failure to have baffles properly installed will severely affect combustion efficiency.
clearances to coMbustibles
Above Top of
From the
From Sides
From Chimney
6 Ft. of
6 Ft. of
Warm Air Plenum
Front
and Back
Connector
Plenum
Plenum
6"
48"
18"*
18"
6"
1"
Up to 50% less clearance between combustible walls and
chimney connector to furnace and ducts is allowed if insu-
lated according to NFPA Standard 90B or your local building
code. This copyrighted book is available from the National
Fire Protection Association Inc. P.O. Box 9101, Quicy, MA
02269-9101.