background image

1

checks and adJustMents

If  you  have  installed  your  own  furnace,  we  ask  that  you  call  for 
an  inspection  by  a  Service  Technician.  The  peace  of  mind  and 
assured  performance  are  well  worth  the  cost  involved. A  techni-
cian  has  the  proper  instruments  to  make  the  necessary  checks 
and adjustments.

furnace bloWer adJustMent

Set adjustable motor pulley so blower will give approximately 90º F 
temperature rise through furnace. After pulley has been adjusted 
check bolt as follows: (see Fig. 18)

The belt is drawn tight during shipment; therefore both belt tension 
and sheave alignment must be rechecked by the installer when the 
furnace is placed in service.

Improper  belt  tension  and  pulley  misalignment  are  the  major 
causes of furnace fan noise and failure of belts and bearings.

Sheave alignment is easily determined with a straight edge held 
across  the  outer  face  of  the  fan  sheave.  The  face  of  the  motor 
sheave should also be parallel to the straight edge at all points.

Proper belt tension is more difficult to determine accurately. Too 
little tension will permit slippage causing belt wear and may cause 
noise  or  squealing  when  the  motor  starts.  Excessive  tension 
increases  motor  load  and  may  cause  the  oil  film  between  shaft 
and  bearing  to  fail. This,  in  turn,  causes  the  bearing  to  seize  or 
burn out.

The proper belt tension is the minimum which will drive the blower 
without slippage. This varies with sheave diameter, fan size, and 
motor starting torque characteristics. The practical belt tension can 
best be determined by actual experience, but when in doubt it is 
better to have the belt too loose rather than too tight. Belt tension
can  be  judged  by  grasping  the  belt  as  shown.  The  belt  should 
be deflected approximately one inch when moderate pressure is 
applied.

air conditioning

See  air  circulating  fan  performance  curve  charts  on  page  21. 
Service  factors  for  factory  furnished  motors  are  1/3  HP  =  1  .35, 
1/2 HP = 1.25, 3/4 HP = 1.15. All motors are Class A with Class 
B insulation.

duct Work and bloWer sPeed adJustMent

Supply and return duct system should be sized properly for efficient 
operation. Normal air temperature rise through the furnace should 
be adjusted to approximately 90º F. Proper blower speed adjust-
ment, in conjunction with adequate duct work are necessary
to achieve this.

A high temperature rise will result in excessive fuel usage, due to
the  high  stack  temperature  that  always  accompanies  a  high  air 
temperature  rise.  It  can  also  cause  premature  heat  exchanger 
failure.

To perform temperature rise check, start furnace and let it run a 
minimum  of  10  minutes  (be  sure  all  duct  work  is  complete  and 
furnace is in its normal operating condition) .Place #1 thermom-
eter in the return near the furnace. Place #2 thermometer in the 
supply  duct  near  the  furnace,  but  not  in  the  plenum.  After  10 
minutes  or  more  operation,  take  thermometer  readings.  Supply 
air  temperature  should  be  no  more  than  90Q  higher  than  return 
air temperature.

Air temperature rise can be lowered by:

1. Increasing blower speed.

2. Additional supply or return outlets .

3. Lowering firing rate.

testing installations for efficiencY

iMPortant

Draft gauge must be used. Draft in smoke pipe must be set at 
.03 Water Column updraft. Failure to set properly will cause fuel 
to  be  wasted,  heating  will  not  be  satisfactory,  fast  build-up  of 
creosote in heat exchanger and chimney may occur, and cause 
damage to your heating system.

The  draft  regulator  will  afford  the  user  maximum  fuel  efficiency, 
however, the finest draft regulator in the world cannot increase the 
efficiency of a heating system if the system as well as the regulator 
is not in proper adjustment.

Many common tests are available to establish the efficiency of the 
system. One such test is outlined on page 9.

Содержание Klondike Eagle IV

Страница 1: ...pliance Alpha American Co 10 Industrial Blvd Palisade MN 56469 www yukon eagle com YUKON EAGLE OWNER S MANUAL Assembly Installation Operation Repair Parts Model No LW 000 Series CAUTION Read Rules And...

Страница 2: ...d during operation Do not operate with flue draft exceeding 03 W C Do not store flammable materials within marked installa tion clearances Frequently inspect and clean heat exchanger smoke pipe and ch...

Страница 3: ...8 Duct Work and Blower Speed Adjustment 18 Testing Installations for Efficiency 18 Test Procedure 10 MAINTENANCE Cleaning the Chimney Smoke Pipe and Heat Exchanger 19 In Case of Chimney Fire 19 Servic...

Страница 4: ...lt in failure of heat exchanger and cause dangerous operation 4 You must have a sufficient supply of combustion air to the area in which the furnace is located page 4 5 Factory Built Chimneys Connect...

Страница 5: ...should occur be sure ash door and firedoor are closed Turn thermostat down to close primary air damper In the event of an electrical power failure be sure ash door and fire door remain closed In the...

Страница 6: ...eat with second baffle making sure baffles interlock as shown in Fig 6 When properly installed baffles will not move more than 1 4 in any direction Failure to have baffles properly installed will seve...

Страница 7: ...pre selected location making sure it is level Proceed as follows Before Installing check DRAW COLLAR Attach the draw collar around the smoke pipe and tight against the furnace cabinet so room air cann...

Страница 8: ...r and place the 4 square box the furnished wiring harness over cable connector and replace the lock nut Secure the square box to the furnace with two sheet metal screws Connect the 34 long conduit to...

Страница 9: ......

Страница 10: ...ent outward into the collar and thus make a better joint WHEN FINISHED THE OPENING INTO THE FLUE MUST BE EQUAL IN SIZE TO THE COLLAR OF THE DRAFT CONTROL If flue pipe is made of material too heavy to...

Страница 11: ...stible wall is allowed if the space is insulated according to NFPA 90B table 6 5 1 2 DO NOT CONNECT THIS FURNACE TO A CHIMNEY SERVING ANOTHER APPLIANCE The chimney should be no less than 8 inches insi...

Страница 12: ...r chimney must terminate at least 2 feet above the peak of the roof Adding more chimney height sometimes cures the problem See Fig 12 page 14 5 Home located on side of hill When the wind blows over a...

Страница 13: ...You need two grilles each with 180 square inches of free opening Metal grilles have about 60 free open area so you need two metal grilles with 300 square inches each of louvered area The height should...

Страница 14: ...chim ney Outside air is also needed to replace any air expelled by kitchen or bathroom fans as well as water heater chimneys or fans Failure to provide outside air to the area in which the furnace is...

Страница 15: ...verload your furnace with wood Failure or damage to the firebox could result Never allow the hot coals to build up above the lower firebricks BEST WOOD TO BURN All solid fuel whether it is coal pine o...

Страница 16: ...ople and is recommended for use in this furnace Anthracite coal is hard and burns like the charcoal that is used in your barbecue grill The coals must touch each other to ignite Therefore the smaller...

Страница 17: ...e ash pan on a daily basis and should never be allowed to accumulate high enough to come in contact with the grates Such a condition could cut off necessary air circulation and could also result in a...

Страница 18: ...R CONDITIONING See air circulating fan performance curve charts on page 21 Service factors for factory furnished motors are 1 3 HP 1 35 1 2 HP 1 25 3 4 HP 1 15 All motors are Class A with Class B insu...

Страница 19: ...ainer until all cinders have thoroughly cooled CLEANING THE CHIMNEY SMOKE PIPE AND HEAT EXCHANGER Avoid chimney fires On a regular schedule check for creosote and soot buildup in the chimney smoke pip...

Страница 20: ...ht Check for obstruction such as loose mortar bird nests and squirrel nests Clean chimney to eliminate obstructions Check for obstructions in combustion air inlet See page 14 Too cold a chimney will c...

Страница 21: ...21...

Страница 22: ...22 9 10100700 10100700 lower upper...

Страница 23: ...23...

Страница 24: ...24 T 8000...

Страница 25: ...______________________________________________________________ _____________________________________________________________________________________ Notes _____________________________________________...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...TRACTOR ONLINE AT OUR WEBSITE OR FROM OUR FACTORY PHONE 1 800 358 0060 FAX 1 800 440 1994 E MAIL yukon mlecmn net WEBSITE www yukon eagle com Alpha American Co 10 Industrial Blvd Palisade MN 56469 www...

Отзывы: