4.4.4
Double acting actuator – YT-3301
Double acting linear (left) and rotary (right) type actuator
4.5
Connection – Power
4.5.1 Safety
When installing in hazardous and explosive gas area, conduit tube or pressure-proof
packing union must be used. The compound charging box should be the flameproof
type and must be sealed completely.
Conduit entry connection tap is PF 1/2 or G 1/2.
Before connecting terminal, ensure that the power is off completely.
Do not open the
cover when the power is still alive.
Please use ring-type rug to protect against vibration or any other external impact.
Positioner with PTM options must be supplied 10~28V DC separately. For L/S option,
separate 12-24V DC must be supplied.
For both options, it should not exceed 30V
DC.
Positioner should be grounded.
Please use twisted cable with conductor section are 1.25mm
2
and that is suitable for
600V (complying to the conductor table of NEC Article 310.) The outer diameter of the
cable should be between 6.35 ~ 10mm. Use shield wire to protect against electro-
magnetic field and noise.
Please do not install the cable near high noise equipments, such as high-capacity
transformer or motor.
Содержание YT-3300 Series
Страница 1: ...SMART POSITIONER PRODUCT MANUAL YT 3300 3301 SERIES VERSION 1 02...
Страница 4: ...4 YT 3300 3301 series 7 2 Warning Code 33 8 Main Software Map 35...
Страница 10: ...10 YT 3300 3301 series 2 7 Parts and Assembly YT 3301L YT 3301R 2 8 Product Dimension 2 8 1 YT 3300L...
Страница 11: ...11 YT 3300 3301 series 2 8 2 YT 3300R 2 8 2 1 YT 3300R standard 2 8 2 2 YT 3300R with L S option...
Страница 12: ...12 YT 3300 3301 series 2 8 3 YT 3301L 2 8 4 YT 3301R...
Страница 35: ...35 YT 3300 3301 series 8 Main Software Map...