Smart Positioner
YT-1000 / 1050 series
Product Manual
Ver. 1.04
50
5. 20mA button:
The button is used when setting 100% position of full stroke during calibration. Position
the valve at 100%, press and hold the button for 2 seconds and the lamp will flash twice
quickly. Release the button, and then the lamp will flash three times quickly again to
confirm that the new setting has been saved.
6.5
Internal SPTM (With LCD)
Refer to product manual of SPTM-6V or SPMT-5V to calibrate the position transmitter.
Fig. 6-6: Connecting cables