45
6. Connection
– Power
6.1
General
Conduit entry connection tap is G 1/2 (PF 1/2).
Positioner usually uses 4~20mA DC.
Positioner with PTM options must be supplied with
9~28V DC
separately.
Positioner should be grounded.
Please do not install the cable near high noise equipment, such as high-capacity
transformer or motor.
To maintain Type 4 and IP66 rating, when installing threaded conduit, use type PTFE
tape according to instructions.
6.2
Flameproof enclosure type
6.2.1
Safety
When installing in hazardous and explosive gas area, conduit tube or pressure-proof
packing union must be used. The compound charging box should be the flameproof
type and must be sealed completely.
Before connecting terminal, ensure that the power is off completely.
Do not open the
cover when the power is still alive.
Please use ring terminal to protect against vibration or any other external impact.
Please use twisted cable with conductor section are 1.25mm
2
and that is suitable for
600V (complying with the conductor table of NEC Article 310.) The outer diameter of
the cable should be between 6.35 ~ 10mm. Use shield wire to protect against electro-
magnetic field and noise.
Fig. 6-1: Pressure-proof packing union
Fig. 6-2: Flame proof type compound charge box
Содержание YT-1000 series
Страница 1: ...SMART POSITIONER PRODUCT MANUAL YT 1000 1050 SERIES VERSION 1 04 ...
Страница 19: ...Smart Positioner YT 1000 1050 series Product Manual Ver 1 04 19 2 7 3 YT 1000R 2 7 4 YT 1000R SPTM Internal ...
Страница 20: ...Smart Positioner YT 1000 1050 series Product Manual Ver 1 04 20 2 7 5 YT 1000R Limits Switch Internal ...
Страница 27: ...Smart Positioner YT 1000 1050 series Product Manual Ver 1 04 27 2 8 10 YT 1000R External SPTM with LCD ...
Страница 28: ...Smart Positioner YT 1000 1050 series Product Manual Ver 1 04 28 2 8 11 YT 1000R External Limit Switch ...