background image

6000 Series Analog Input Modules 

The Optimal Choice for Harsh Environment 

 

-6018 Thermocouple Analog Input Module   

 

1.  Introduction 

 
NuDAM-6018  is  a  thermocouple  input  module  with  8  input 
channels.  Six  of  the  eight  channels  are  differential  and  the 
other two are single ended type.   
 

Features 

 

 

8 analog input channels 

 

6 differential input and 2 single ended input 

 

programmable input range   

 

programmable  host  watchdog  timer  for  host  failure 

protection 

 

on board CJC for temperature measurement 

 

2500 Vrms analog input isolation 

 

internal watchdog timer for device failure protection 

 

easy programming by software 

 

easy installation and wiring 

 

 

Specifications 

 

 

Interface:   

RS-485, 2 wires 
Speed (bps): 600, 1200, 2400, 4800, 9600, 19.2k, 
38.4k, 57.6k, 115.2k 

 

Analog Input:   

Differential channels: 6   
Single ended channels: 2 
Resolution: 16 bits 
Accuracy: ±0.05%   
Sampling rate: 10   
Unit conversion: thermocouple, mV, V or mA 
Thermocouple type: J, K, T, E, R, S, B, N and C 
J: 0

C ~ 760

C    K: 0

C ~ 1370

T: -100

C ~ 400

C   

E: 0

C ~ 1000

R: 500

C ~ 1750

S: 500

C ~ 1750

B: 500

C ~ 1800

N: -270

C ~ 1300

C: 0

C ~ 2320

Voltage range: programmable 6 levels: 
±2.5V, ±1V, ±500mV, ±100mV, ±50mV, ±15mV   
Current  measurement:  20mA  (with  external  125 
ohm resistor)   
Isolation Voltage: 2500 Vrms 

Note:  The  maximum  input  voltage  shall  not 
exceed  to  ±30V  with  reference  to  AGND 
otherwise,  they  may  cause  an  unrecoverable 
harm to the hardware component. 

 

Storage Temperature Range: -25 to 80 

 

Operating Temperature Range: -10 to 70 

 

Power  Requirement:  +10V  to  +30V

DC 

Unregulated 

with against power reversal 

 

Power Consumption: 0.70W 

 

Case: ABS with captive mounting hardware 

 

CE Class A Conformity   

 

2.  Pin Assignment 
 

ND-6018

(Y)
DA
TA

+

(G)
DA
TA
-

(R)
+V

s

(B)
GN

D

8-CH Thermocouple
Input

1

10

Vin

5+

Vin

5-

Vin

6+

AG

ND

Vin

7+

DE
FA
UL

T

*

Vin

4-

Vin

4+

Vin

3-

Vin

3+

Vin

2-

Vin

2+

Vin

1-

Vin

1+

Vin

0-

Vin

0+

11

20

0E

0F

10

11

12

J

K

T

E

R

S

CODE

T/C

13

 

 
 

Pin Definitions 

 

Pin #  Signal Name  Description 

Vin5+ 

Differential positive input channel 5 

Vin5- 

Differential negative input channel 5 

Vin6+ 

Single-ended input channel 6   

AGND 

Analog signal ground of channel 6 & 7 

Vin7+ 

Single-ended input channel 7   

DEFAULT*  Initial state setting   

(Y)DATA+ 

RS-485 signal, positive   

(G)DATA- 

RS-485 signal, negative   

(R)+VS 

Power supply, +10V ~ +30Vdc 

10 

(B)GND 

Ground   

11 

Vin0+ 

Differential positive input channel 0 

12 

Vin0- 

Differential negative input channel 0 

13 

Vin1+ 

Differential positive input channel 1 

14 

Vin1- 

Differential negative input channel 1 

15 

Vin2+ 

Differential positive input channel 2 

16 

Vin2- 

Differential negative input channel 2 

17 

Vin3+ 

Differential positive input channel 3 

18 

Vin3- 

Differential negative input channel 3 

19 

Vin4+ 

Differential positive input channel 4 

20 

Vin4- 

Differential negative input channel 4 

 

*The  module  is  in  DEFAULT  mode  when  DEFAULT*  pin 
connected to GND while applying power on the module. 
*Do not apply any power signal to DEFAULT* pin, just left 
it open or connected it to GND. 

 

 
 
 

3.  Application Wiring 

Differential Voltage Input   

 

AGND

AGND

               

Differential
Signal
Source

<30V

IN(-)

IN(+)

ADC

 

 

 

Single Ended Voltage Input   

 

             

Ground
Signal
Source

AGND

IN(+)

ADC

 

 

Current Input Measurement   

 

Current
Source

R=125 Ohm
%1 accuracy

IN(-)

IN(+)

ADC

R

 

 

Thermocouple Input Measurement   

 

<30V

IN(-)

IN(+)

ADC

AGND

AGN D

 

 

4.  Functional Block Diagram 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

5.  Installation 

 

Equipment for Installation   

 

A existing RS-485 network   
NuDAM modules 
DC Power supply (+10V~+30V) 
Wires for power, communication and I/O signal   
 

Installation Procedure 

1.

 

Configure  every  single  NuDAM  module  under  the 
administration utility   

2.

 

The baud rate setting and calibration procedure must be 
done under the DEFAULT* mode 

3.

 

The  baud  rate  and  check-sum  status  must  be  identity 
with  the  application  network.  The  address  ID  must  not 
be conflict with other modules on the network 

4.

 

Plug the new module to the existing network   

5.

 

Use  the  NuDAM  administration  utility  to  check  the 
entire network 

 
 
 
 
 
 
 
 
 
 
 
 
 

Power Input 
+10V ~ +30V 

+ 5V 

Power 

Regulator & Filter 

Data+ 

Data - 

GND 

RS-485 

Rec/Drv 

 

Micro 

Processor 

EEPROM 

Config Data 

Safe Value 

 

ADC 

 

1-bit 

Digital Input 

Thermo- 

couple 

Input 

channels 

Default* 
Pin 

 

Mux 

 

Watchdog/Power Failure 

Supervisor 