YO Power
User guide
v4.0
page 7/28
Operating conditions
OPERATING CONDITIONS
Temperature
0° to 70°C
Humidity
0 to 90%
Placement
Indoor use
Power supply
6 - 30 V DC
5 - 21 V AC
Power consumption
Typical: 12 mA DC (12 V DC)
Maximum: 120 mA DC (12 V DC)
Measured values
MEASUREMENT RANGES
Parameter
Measuring range
Accuracy
Current
CT Model : 50mA-100 A
±1%
CT Model : 40mA-160A
±3%
CT Model : 50mA-200 A
±3%
CT Model : 50mA-400 A
±3%
CT Model : 50mA-600 A
±3%
CT Model : 50mA-800 A
±3%
CT Model : 50mA-1000 A
±3%
Power consumption
0-230 V
Not given in datasheet
Current
YO Power offers automatically switchable measurement ranges: 2 A, 10 A, 50 A, 100 A., which
results in even greater precision when measuring current. Each channel can measure current over
different measuring ranges simultaneously. The YO Power has measurement inputs with specialized
integrated circuits (e.g. specialized analog-to-digital converters) that ensure high measurement
accuracy.