24
Johnson Controls Unitary Products
632151-YTG-A-1010
Multipliers for determining the performance with other indoor sections.
NOTE:
KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YZF03613(C)
INDOOR COIL MODEL NO.
AHX42
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1000
1200
1400
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
44.7
3.64
3.1
44.9
3.96
2.9
45.0
4.35
2.7
70
43.8
3.20
3.5
44.1
3.48
3.3
44.3
3.83
3.0
80
42.9
2.83
3.9
43.3
3.10
3.6
43.7
3.41
3.4
47
60
38.5
3.35
2.8
38.4
3.63
2.7
38.3
3.96
2.5
70
37.7
2.95
3.2
37.8
3.19
3.0
37.9
3.47
2.8
80
36.9
2.62
3.6
37.2
2.83
3.4
37.4
3.09
3.2
40
60
34.7
3.10
2.8
34.7
3.34
2.6
34.8
3.63
2.4
70
34.1
2.74
3.1
34.3
2.96
2.9
34.5
3.22
2.8
80
33.5
2.44
3.5
33.8
2.65
3.3
34.1
2.89
3.1
30
60
30.5
2.87
2.6
30.6
3.08
2.5
30.6
3.33
2.3
70
29.8
2.51
3.0
30.0
2.70
2.8
30.1
2.91
2.7
80
29.1
2.22
3.3
29.4
2.39
3.2
29.7
2.58
3.0
17
60
24.6
1.96
3.2
24.9
2.31
2.7
25.1
2.82
2.2
70
24.1
1.91
3.2
24.4
2.17
2.8
24.8
2.50
2.5
80
23.5
1.87
3.2
24.0
2.04
3.0
24.4
2.24
2.8
10
60
21.8
2.31
2.2
21.2
2.38
2.2
20.6
2.45
2.1
70
21.3
2.04
2.5
21.0
2.17
2.4
20.6
2.32
2.2
80
20.8
1.82
2.8
20.7
1.99
2.6
20.6
2.19
2.4
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
AHX48
–
1.00
1.02
0.98
AV*48
–
1.01
1.05
0.96
F6FP042
–
1.01
1.02
1.00
F6FP048
–
1.00
1.03
0.97
MV12D
FC/MC48D
0.99
1.00
1.00
MV16C
FC/MC48C
1.00
0.98
1.02
MV12D
FC/MC60D
1.01
1.03
0.98
Furnace
Coil
MBH
KW
COP
T*(8,L)X*C16
FC/MC/PC48C
0.99
1.00
1.00
T*(8,L)X*C20
FC/MC/PC48C
1.00
1.01
0.99
T*9X*C16
FC/MC/PC48C
1.01
1.00
1.01
T*9X*C20
FC/MC/PC48C
1.00
0.98
1.02
T*9X*D20
FC/MC/PC48D
1.01
1.01
1.00
(Y*(8,L)C/T*8V)*C16
FC/MC/PC48C
1.00
0.98
1.03
(Y*(8,L)C/T*8V)*C20
FC/MC/PC48C
1.00
0.98
1.02
(Y*9C/T*9V)*D20
FC/MC/PC48D
1.01
0.99
1.02
T*(8,L)X*C16
FC/PC60C
1.00
1.04
0.96
T*(8,L)X*C20
FC/PC60C
1.01
1.06
0.96
T*9X*C16
FC/PC60C
1.02
1.05
0.97
T*9X*C20
FC/PC60C
1.01
1.05
0.97
T*9X*D20
FC/MC/PC60D
1.01
1.07
0.94
(Y*(8,L)C/T*8V)*C16
FC/PC60C
1.01
1.03
0.98
(Y*(8,L)C/T*8V)*C20
FC/PC60C
1.01
1.04
0.98
(Y*9C/T*9V)*D20
FC/MC/PC60D
1.02
1.03
0.99
T*(8,L)X*C16
UC48C
1.00
1.04
0.96
T*(8,L)X*C20
UC48C
1.01
1.04
0.97
T*9X*C16
UC48C
1.01
1.03
0.99
T*9X*C20
UC48C
1.01
1.02
0.99
T*9X*D20
UC48D
1.01
1.03
0.98
(Y*(8,L)C/T*8V)*C16
UC48C
1.01
1.02
0.99
(Y*(8,L)C/T*8V)*C20
UC48C
1.01
1.03
0.98
T*(8,L)X*C16
UC60C
1.00
1.04
0.96
T*(8,L)X*C20
UC60C
1.01
1.04
0.97
T*9X*C16
UC60C
1.01
1.04
0.98
T*9X*C20
UC60C
1.01
1.02
0.99
T*9X*D20
UC60D
1.01
1.06
0.95
(Y*(8,L)C/T*8V)*C16
UC60C
1.01
1.02
0.99
(Y*(8,L)C/T*8V)*C20
UC60C
1.01
1.02
0.99
Furnace
Coil
MBH
KW
COP