18
Johnson Controls Unitary Products
632151-YTG-A-1010
Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE:
KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
COOLING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YZF04213(C)
INDOOR COIL MODEL NO.
AHX60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM
1185
1385
1585
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
57
62
62
67
72
57
65
T.C.
39.7
42.3
42.3
46.2
50.6
41.4
43.5
43.4
47.5
51.9
43.2
44.7
44.6
48.7
53.3
S.C.
37.5
33.8
29.1
29.0
24.1
39.1
36.7
31.1
30.8
25.2
40.8
39.6
33.0
32.6
26.2
K.W.
2.37
2.38
2.37
2.37
2.37
2.45
2.46
2.45
2.45
2.46
2.52
2.53
2.53
2.53
2.54
75
T.C.
38.3
40.4
40.5
44.2
48.4
40.0
41.5
41.5
45.4
49.6
41.8
42.6
42.5
46.5
50.9
S.C.
36.2
33.1
28.4
28.2
23.2
37.8
35.8
30.3
30.0
24.2
39.4
38.4
32.2
31.9
25.3
K.W.
2.70
2.70
2.70
2.71
2.72
2.78
2.78
2.78
2.79
2.81
2.86
2.86
2.86
2.88
2.89
85
T.C.
37.0
38.5
38.7
42.2
46.2
38.6
39.4
39.6
43.3
47.3
40.3
40.4
40.4
44.3
48.4
S.C.
34.9
32.5
27.7
27.4
22.3
36.5
34.9
29.5
29.2
23.3
38.1
37.3
31.4
31.1
24.3
K.W.
3.02
3.02
3.03
3.05
3.07
3.11
3.11
3.11
3.13
3.16
3.20
3.19
3.19
3.22
3.24
95
T.C.
35.6
36.6
36.9
40.2
44.0
37.2
37.4
37.6
41.2
45.0
38.9
38.2
38.3
42.2
45.9
S.C.
33.6
31.8
26.9
26.6
21.4
35.2
34.0
28.8
28.4
22.4
36.7
36.1
30.6
30.3
23.4
K.W.
3.34
3.34
3.36
3.38
3.42
3.44
3.43
3.44
3.48
3.51
3.55
3.52
3.52
3.57
3.60
105
T.C.
33.8
34.4
34.6
37.8
41.5
35.3
35.4
35.1
38.6
42.2
36.8
36.5
35.7
39.3
43.0
S.C.
31.9
31.0
26.0
25.7
20.5
33.3
32.7
27.8
27.5
21.4
34.8
34.4
29.7
29.3
22.4
K.W.
3.71
3.64
3.64
3.67
3.71
3.77
3.73
3.73
3.76
3.80
3.83
3.82
3.81
3.85
3.88
115
T.C.
32.0
32.2
32.2
35.4
38.9
33.3
33.4
32.7
35.9
39.5
34.7
34.7
33.1
36.5
40.0
S.C.
30.2
30.1
25.1
24.8
19.6
31.5
31.4
26.9
26.6
20.5
32.8
32.8
28.7
28.3
21.4
K.W.
4.07
3.93
3.93
3.96
4.00
4.09
4.02
4.01
4.04
4.08
4.12
4.12
4.09
4.13
4.17
125
T.C.
30.1
30.0
29.8
33.0
36.4
31.4
31.4
30.2
33.3
36.7
32.6
32.9
30.5
33.6
37.1
S.C.
28.5
29.3
24.1
23.9
18.6
29.6
30.2
26.0
25.6
19.5
30.8
31.1
27.8
27.4
20.4
K.W.
4.43
4.22
4.21
4.24
4.29
4.42
4.32
4.30
4.32
4.37
4.40
4.41
4.38
4.41
4.45
NOTE:
ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler
Coil
T.C.
S.C.
KW
F6FP060
–
1.01
1.02
1.06
MV20D
FC/MC62D
1.00
1.00
1.05
Furnace
Coil
T.C.
S.C.
KW
T*(8,L)X*C16
FC/MC62D
1.00
0.99
1.05
T*(8,L)X*C20
FC/MC62D
1.01
1.03
1.06
T*9X*C16
FC/MC62D
1.01
1.02
1.06
T*9X*C20
FC/MC62D
1.01
1.03
1.06
T*9X*D20
FC/MC62D
1.01
1.03
1.06
(Y*(8,L)C/T*8V)*C16
FC/MC62D
1.01
1.02
1.06
(Y*(8,L)C/T*8V)*C20
FC/MC62D
1.00
0.99
1.05
(Y*9C/T*9V)*D20
FC/MC62D
1.01
1.02
1.06