York YZ Скачать руководство пользователя страница 19

YZ Engineering Guide

 

Form: 161.01-EG1 (0618)

 

 

 

19 

 
connections. If desired, vent and drain valves may be installed with or without piping to an open drain. Pressure gauges 
with stop-cocks and stop-valves may be installed in the inlets and outlets of the condenser and chilled water line as close 
as possible to the chiller. An overhead monorail or beam may be used to facilitate servicing. 

 

Connections 

-  The  standard  chiller  is  designed  for  1034  kPa  (150  psig)  design  working  pressure  in  both the  chilled 

water  and  condenser  water  circuits.  The  connections  (water  nozzles)  to  these  circuits  are  furnished  with  grooves  to 
ANSI/AWWA C-606 standard for grooved and shouldered joints. Piping should be arranged for ease of disassembly at 
the unit for tube cleaning. All water piping should be thoroughly cleaned of all dirt and debris before final connections are 
made to the chiller. 
 

Chilled Water 

- A water strainer of maximum 3.2 mm (1/8") perforated holes must be field-installed in the chilled water 

inlet line as close as possible to the chiller. If located close enough to the chiller, the chilled water pump may be protected 
by the same strainer. The strainer is important to protect the chiller from debris or objects which could block flow through 
individual heat exchanger tubes. A reduction in flow through tubes could seriously impair the chiller performance or even 
result in tube freeze-up. A flow switch is factory installed in the evaporator nozzle and connected to the OptiView

™ panel, 

which assures adequate chilled water flow during operation. 
 

Condenser Water

 - The chiller is engineered for maximum efficiency at both design and part load operation by taking 

advantage of the colder cooling tower water temperatures which naturally occur during the winter months. Appreciable 
power savings are realized from these reduced heads. At initial startup, entering condensing water temperature may be 
as much as 16.7°C (30°F) colder than the standby chilled water temperature.  
 

MULTIPLE UNITS 

 
Selection
 

-

 

Many applications require multiple units to meet the total capacity requirements as well as to provide flexibility 

and some degree of protection against equipment shutdown. There are several common unit arrangements for this type 
of application. The YZ chiller has been designed to be readily adapted to the requirements of these various arrangements.  
 

Parallel  Arrangement 

-

 

Chillers  may  be  applied  in  multiples  with  chilled  and  condenser  water  circuits  connected  in 

parallel  between  the  units.  Figure  1  below  represents  a  parallel  arrangement  with  two  chillers.  Parallel  chiller 
arrangements may consist of equally or unequally sized units. When multiple units are in operation, they will load and 
unload at equal percentages of design full load for the chiller.  
 

Figure 1

 

– Parallel Evaporators (Evap.) Parallel Condensers (Cond.) 

Cond. 1

 

Evap. 1

 

Cond. 2

 

Evap. 2

 

T

 

S1

 

S2

 

T

 

S

 

- Thermostat for Chiller Capacity Control

 

- Temperature Sensor for Chiller Capacity Control

 

Содержание YZ

Страница 1: ...ENGINEERING GUIDE YORK YZ Centrifugal Chiller Form 161 01 EG1 0618 MODEL YZ MAGNETIC BEARING CENTRIFUGAL CHILLER Style A 580 through 3500 kW 165 through 1000 Tons Utilizing R 1233zd...

Страница 2: ...01 EG1 0618 2 Table of Contents Nomenclature 3 Introduction 4 Unit Components 6 Equipment Overview 8 Codes and Standards 14 Chiller Options 16 Application Data 17 Unit Weights Dimensions 22 Visit YORK...

Страница 3: ...no filter H harmonic filter VSD Cooling Product Family Motor Name Compressor Name Unit Mod Level VSD Name Motor Family Motor Size Code Motor Configuration Level Compressor Family Compressor Size Code...

Страница 4: ...ximum chiller efficiency under actual not just theoretical operating conditions Now with the YORK YZ efficiency is improved up to an impressive 7 at part load and as much as an additional 5 at full lo...

Страница 5: ...ice design principles that are consistent with our family of centrifugal chillers We made sure that this chiller and specifically the driveline was field serviceable by a single source supplier who al...

Страница 6: ...YZ Engineering Guide Form 161 01 EG1 0618 6 Unit Components Suction Line Endsheet OptiView Control Panel Condenser Sight Glass Lockout Handle Variable Speed Drive Discharge Line...

Страница 7: ...YZ Engineering Guide Form 161 01 EG1 0618 7 Unit Components Continued VSD Coolant Reservoir Refrigerant Purge Unit Compact Waterbox Evaporator Direct Drive Compressor Motor...

Страница 8: ...trol is achieved by the combined use of variable speed control and mechanical flow regulation to provide fully modulating control from maximum to minimum load For normal air conditioning applications...

Страница 9: ...and voltage of the electrical power to the motor The capacity control logic shall automatically adjust motor speed and compressor diffuser geometry for maximum part load efficiency by analyzing infor...

Страница 10: ...the OptiView control panel OPTIVIEW CONTROL CENTER Note Please refer to the YZ Operations Maintenance Manual 161 01 OM1 for a complete description of features and functionality The YORK OptiView Cont...

Страница 11: ...sheets drilled and reamed to accommodate the tubes are welded to the end of each shell Intermediate tube supports are fabricated from carbon steel plates and drilled and reamed to eliminate sharp edg...

Страница 12: ...Flow Control Refrigerant flow to the evaporator is controlled by the YORK variable orifice control system Liquid refrigerant level is continuously monitored to provide optimum subcooler condenser and...

Страница 13: ...rt Equipment by Johnson Controls allows the connection of data streams from equipment to the cloud providing unprecedented insights into operations Smart Equipment helps maximize system control for gr...

Страница 14: ...m 7 Driveline separate from split shells Shipped as four major subassemblies with refrigerant charge shipped separately This form is best used when the chiller must fit through a tight space limited b...

Страница 15: ...7012 KHK High Pressure Gas Control Law ELECTRICAL CODES c U L Underwriters Laboratory N E C National Electrical Code CE Directive 93 68 EEC IP Ingress Protection GB 5226 1 ETL Electrical Testing Labs...

Страница 16: ...psig DWP Corrosion protection None Internally epoxy coated waterboxes and tubesheets sacrificial anodes Unit Configuration Ability to isolate refrigerant charge in the condenser None Isolation valves...

Страница 17: ...ther valve while the unit is fully charged The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge as a safety precaution in the event of an emergency such as...

Страница 18: ...many cases but do require more sophisticated control and flow monitoring YZ chillers will operate successfully in VPF systems With a minimum allowable evaporator tube velocity of 0 5m s 1 5 fps for s...

Страница 19: ...tube freeze up A flow switch is factory installed in the evaporator nozzle and connected to the OptiView panel which assures adequate chilled water flow during operation Condenser Water The chiller is...

Страница 20: ...to the desired temperature Figure 2 Series Parallel Arrangement Series Counter Flow Arrangement Chillers may be applied in pairs with chilled water circuits connected in series and with the condenser...

Страница 21: ...0 380 342 423 50 Hz 415 415 374 456 400 400 360 440 380 380 342 423 Copper Conductors Only copper conductors should be connected to compressor motors and starters Aluminum conductors have proven to be...

Страница 22: ...YZ Engineering Guide Form 161 01 EG1 0618 22 Unit Weights Dimensions B Min of 915 mm 3 ft Min of 610 mm 2 ft Service Clearance C A Min of 610 mm 2 ft D...

Страница 23: ...3314 2 9 m 9 4 2 4 m 7 9 4 3 m 14 4 3 m 14 11750kg 25900 lb FA3914 CA3314 3 1 m 10 0 2 4 m 7 9 4 3 m 14 4 3 m 14 12800 kg 28200 lb FA3916 SA3916 3 3 m 10 7 2 6 m 8 5 4 9 m 16 4 9 m 16 16050 kg 35350 l...

Страница 24: ...VE OUR NATURAL RESOURCES THINK BEFORE YOU PRINT Copyright by Johnson Controls 2017 Form 161 01 EG1 Issue Date June 2018 Supersedes 161 01 EG1 1217 Subject to change without notice ALL RIGHTS RESERVED...

Отзывы: