York YZ Скачать руководство пользователя страница 17

YZ Engineering Guide

 

Form: 161.01-EG1 (0618)

 

 

 

17 

 

Application Data 

 
The following is a guide to the application of YZ chillers to ensure reliable operation. While this guide is directed 
towards normal, water-chilling applications, a Johnson Controls sales engineer can provide complete 
recommendations on other types of applications. 
 

LOCATION 

 
YZ chillers are virtually vibration free and may generally be located at any level in a building where the construction will 
support the total system operating weight.  
 
The unit site must be a floor, mounting pad or foundation which is level within 6.5 mm (1/4") and capable of supporting 
the operating weight of the unit.  
 
Sufficient clearance to permit normal service and maintenance work should be provided all around and above the unit. 
Additional space should  be provided at one  end of the unit to permit  cleaning of evaporator  and condenser tubes as 
required. A doorway or other properly located opening may be used if convenient.  
 
The chiller should be installed in an indoor location where temperatures range from 4.4°C to 40.0°C (40°F to 104°F). 
The dew point temperature in the equipment room must be below the entering condenser water temperature to prevent 
condensing water vapor inside of the VSD. Other areas susceptible to water vapor condensate are outside of the 
condenser shell and condenser waterboxes. Example applications include cooling condenser water using chilled water, 
wells, river, or other low temperature fluids.  
 

Refrigerant Relief Piping 

-

 

Each chiller is equipped with dual pressure relief valves on the condenser and two dual relief 

valves  on  the  evaporator,  or  two  single  relief  valves  on  the  evaporator  if  the  optional  refrigerant  isolation  valves  are 
ordered. The dual relief valves on the condenser are redundant and allow changing of either valve while the unit is fully 
charged.  The  purpose  of  the  relief  valves  is  to  quickly  relieve  excess  pressure  of  the  refrigerant  charge,  as  a  safety 
precaution in the event of an emergency such as a fire. They are set to relieve at an internal pressure as noted on the 
pressure vessel data plate, and are provided in accordance with local pressure vessel codes.  
 
Sized to the requirements of applicable codes, a vent line must run from the relief device to the outside of the building. 
This refrigerant relief piping must include a cleanable, vertical leg dirt trap to catch vent-stack condensation. Vent piping 
must be arranged to avoid imposing a strain on the relief connection and should include one flexible connection. 
 

Sound and Vibration Considerations 

- A YZ chiller is not a source of objectionable vibration in most air conditioning 

applications. Standard neoprene isolation mounts are available with each unit to reduce vibration transmission. Optional 
level-adjusting  spring  isolator  assemblies  designed  for  25.4  mm  (1")  static  deflection  are  also  available  for  further 
isolation.  YZ  chiller  sound  pressure  level  ratings  will  be  provided  upon  request.  Control  of  sound  and  vibration 
transmission must be taken into account in the equipment room construction as well as in the selection and installation 
of the equipment.  
 

Thermal Insulation 

-

 

The chiller’s cold surfaces should be insulated with a vapor barrier insulation sufficient to prevent 

condensation.  As  an  option,  a  chiller  can  be  factory-insulated.  This  insulation  will  normally  prevent  condensation  in 
environments with dry bulb temperatures of 10.0°C to 32.2°C (50°F to 90°F) and relative humidity up to 75% [19 mm 
(3/4")  thickness]

, 85% [25.4 mm (1”) thickness], or 90% [38 mm (1.5") thickness]. It is intended for a chiller installed 

indoors  and,  therefore,  no  protective  covering  of  the  insulation  is  usually  required.  If  insulation  is  applied  to  the 
waterboxes at the job site, it must be removable to permit access to the tubes for routine maintenance. 
 
 
 

Содержание YZ

Страница 1: ...ENGINEERING GUIDE YORK YZ Centrifugal Chiller Form 161 01 EG1 0618 MODEL YZ MAGNETIC BEARING CENTRIFUGAL CHILLER Style A 580 through 3500 kW 165 through 1000 Tons Utilizing R 1233zd...

Страница 2: ...01 EG1 0618 2 Table of Contents Nomenclature 3 Introduction 4 Unit Components 6 Equipment Overview 8 Codes and Standards 14 Chiller Options 16 Application Data 17 Unit Weights Dimensions 22 Visit YORK...

Страница 3: ...no filter H harmonic filter VSD Cooling Product Family Motor Name Compressor Name Unit Mod Level VSD Name Motor Family Motor Size Code Motor Configuration Level Compressor Family Compressor Size Code...

Страница 4: ...ximum chiller efficiency under actual not just theoretical operating conditions Now with the YORK YZ efficiency is improved up to an impressive 7 at part load and as much as an additional 5 at full lo...

Страница 5: ...ice design principles that are consistent with our family of centrifugal chillers We made sure that this chiller and specifically the driveline was field serviceable by a single source supplier who al...

Страница 6: ...YZ Engineering Guide Form 161 01 EG1 0618 6 Unit Components Suction Line Endsheet OptiView Control Panel Condenser Sight Glass Lockout Handle Variable Speed Drive Discharge Line...

Страница 7: ...YZ Engineering Guide Form 161 01 EG1 0618 7 Unit Components Continued VSD Coolant Reservoir Refrigerant Purge Unit Compact Waterbox Evaporator Direct Drive Compressor Motor...

Страница 8: ...trol is achieved by the combined use of variable speed control and mechanical flow regulation to provide fully modulating control from maximum to minimum load For normal air conditioning applications...

Страница 9: ...and voltage of the electrical power to the motor The capacity control logic shall automatically adjust motor speed and compressor diffuser geometry for maximum part load efficiency by analyzing infor...

Страница 10: ...the OptiView control panel OPTIVIEW CONTROL CENTER Note Please refer to the YZ Operations Maintenance Manual 161 01 OM1 for a complete description of features and functionality The YORK OptiView Cont...

Страница 11: ...sheets drilled and reamed to accommodate the tubes are welded to the end of each shell Intermediate tube supports are fabricated from carbon steel plates and drilled and reamed to eliminate sharp edg...

Страница 12: ...Flow Control Refrigerant flow to the evaporator is controlled by the YORK variable orifice control system Liquid refrigerant level is continuously monitored to provide optimum subcooler condenser and...

Страница 13: ...rt Equipment by Johnson Controls allows the connection of data streams from equipment to the cloud providing unprecedented insights into operations Smart Equipment helps maximize system control for gr...

Страница 14: ...m 7 Driveline separate from split shells Shipped as four major subassemblies with refrigerant charge shipped separately This form is best used when the chiller must fit through a tight space limited b...

Страница 15: ...7012 KHK High Pressure Gas Control Law ELECTRICAL CODES c U L Underwriters Laboratory N E C National Electrical Code CE Directive 93 68 EEC IP Ingress Protection GB 5226 1 ETL Electrical Testing Labs...

Страница 16: ...psig DWP Corrosion protection None Internally epoxy coated waterboxes and tubesheets sacrificial anodes Unit Configuration Ability to isolate refrigerant charge in the condenser None Isolation valves...

Страница 17: ...ther valve while the unit is fully charged The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge as a safety precaution in the event of an emergency such as...

Страница 18: ...many cases but do require more sophisticated control and flow monitoring YZ chillers will operate successfully in VPF systems With a minimum allowable evaporator tube velocity of 0 5m s 1 5 fps for s...

Страница 19: ...tube freeze up A flow switch is factory installed in the evaporator nozzle and connected to the OptiView panel which assures adequate chilled water flow during operation Condenser Water The chiller is...

Страница 20: ...to the desired temperature Figure 2 Series Parallel Arrangement Series Counter Flow Arrangement Chillers may be applied in pairs with chilled water circuits connected in series and with the condenser...

Страница 21: ...0 380 342 423 50 Hz 415 415 374 456 400 400 360 440 380 380 342 423 Copper Conductors Only copper conductors should be connected to compressor motors and starters Aluminum conductors have proven to be...

Страница 22: ...YZ Engineering Guide Form 161 01 EG1 0618 22 Unit Weights Dimensions B Min of 915 mm 3 ft Min of 610 mm 2 ft Service Clearance C A Min of 610 mm 2 ft D...

Страница 23: ...3314 2 9 m 9 4 2 4 m 7 9 4 3 m 14 4 3 m 14 11750kg 25900 lb FA3914 CA3314 3 1 m 10 0 2 4 m 7 9 4 3 m 14 4 3 m 14 12800 kg 28200 lb FA3916 SA3916 3 3 m 10 7 2 6 m 8 5 4 9 m 16 4 9 m 16 16050 kg 35350 l...

Страница 24: ...VE OUR NATURAL RESOURCES THINK BEFORE YOU PRINT Copyright by Johnson Controls 2017 Form 161 01 EG1 Issue Date June 2018 Supersedes 161 01 EG1 1217 Subject to change without notice ALL RIGHTS RESERVED...

Отзывы: