YZ Engineering Guide
Form: 161.01-EG1 (0618)
14
SHIPMENT
Each unit can be broken down into several form shipment configurations for ease of transportation and installation. For
all broken down shipment options, the unit is first factory assembled, refrigerant piped, wired and leak tested; then
disassembled according to the shipment option selected.
Protective covering is furnished on the OptiView
™ and VSD. Water nozzles are capped with fitted plastic enclosures.
Then the entire unit is protected with industrial-grade, reinforced shrink-wrap covering.
Form 1
–
Unit is shipped as one assembly with refrigerant charge inside the unit.
Form 2
– Unit is shipped as one assembly with refrigerant charge shipped separately.
Form 3
– Driveline separate from shells. Shipped as three major subassemblies with refrigerant charge shipped
separately. This form is best used when height is a limiting dimension to enter the installation site.
Driveline (motor/compressor assembly)
Evaporator/Condenser shell assembly
– not skidded
Variable Speed Drive
Form 7
– Driveline separate from split shells. Shipped as four major subassemblies, with refrigerant charge shipped
separately. This form is best used when the chiller must fit through a tight space, limited by multiple dimensions.
Driveline (motor/compressor assembly)
Evaporator
– not skidded
Condenser
– not skidded
Variable Speed Drive
Form 11
– Unit shipped as two major subassemblies, with refrigerant charge shipped separately. This form is best used
when width is a limiting dimension to enter the installation site.
Condenser side assembly (Condenser/OptiView
™/Variable Speed Drive) – not skidded
Evaporator side assembly (Evaporator/Driveline/Magnetic Bearing Controller)
– not skidded
Codes and Standards
Chiller standards and codes vary based on factory source. Any of the standards and codes listed below can be met when
ordering the YZ chiller. Work with your local sales contact for a unit that will meet your local codes and standards.
PERFORMANCE & ENERGY STANDARDS
ASHRAE 90.1
AHRI Standard 550/590
IECC
– International Energy Conservation Code
GBCI
– Green Business Certification Inc.
Eurovent (EN14511, EN14825)
GB 18430.1
GB 19577/GB 50189
GB/T 50378
MEPS
– Minimum Energy Performance Standards
ECBC
– Energy Conservation Building Code
Greenmark