York YZ Скачать руководство пользователя страница 18

YZ Engineering Guide

 

Form: 161.01-EG1 (0618)

 

 

 

18 

 

Ventilation 

- Some standards requires that all machinery rooms be vented to the outdoors utilizing mechanical ventilation 

by one or more fans. State, local and any other related codes should be reviewed for specific requirements. Since the 
YZ chiller motor is hermetically sealed, no additional ventilation is needed due to motor heat.  

 

In addition, the ASHRAE Standard 15 requires a refrigerant vapor detector to be employed for all refrigerants. It is to be 
located  in  an  area  where  refrigerant  from  a  leak  would  be  likely  to  concentrate.  An  alarm  is  to  be  activated  and  the 
mechanical ventilation started at a value no greater than the Threshold Limit Value (TLV) of the refrigerant. 
 

WATER CIRCUITS 

 

Flow Rate

 - For normal water chilling duty, evaporator and condenser flow rates are permitted at water velocity levels in 

the heat exchanger tubes of between 0.91m/s and 3.66m/s (3.0 fps and 12.0 fps) for evaporators and 1.0m/s and 3.66m/s 
(3.3 fps and 12.0 fps) for condensers. Two pass units are also limited to 134kPa (45ft H

2

O) water pressure drop. The 

three pass limit is 201kPa (67.5ft H

2

O). Variable flow in the condenser is not recommended, as it generally raises the 

energy consumption of the system by keeping the condenser pressure high in the chiller. Additionally, the rate of fouling 
in the condenser will increase at lower water velocities associated with variable flow, raising system maintenance costs. 
Cooling towers typically have narrow ranges of operation with respect to flow rates, and will be more effective with full 
design flow.  
 
The chillers can tolerate a 50% flow rate change in one minute that is typically associated with the staging on or off of an 
additional  chiller;  however  a  lower  flow  rate  change  is  normally  used  for  better  system  stability  and  set point control. 
Proper sequencing via the building automation system will make this a very smooth transition. 
 

Variable Primary Flow

 - There is increasing interest to use variable primary flow (VPF) systems in large chilled water 

plants. VPF systems can offer lower installation and operating costs in many cases, but do require more sophisticated 
control and flow monitoring. YZ chillers will operate successfully in VPF systems. With a minimum allowable evaporator 
tube velocity of 0.5m/s (1.5 fps) for standard tubes at part load rating conditions, YZ chillers will accommodate the wide 
variation in flow required by many chilled water VPF applications. 
 

Temperature  Ranges

  -

 

For  normal  water  chilling  duty,  leaving  chilled  water  temperatures  may  be  selected  between 

3.5°C  (38°F)  and  21.0°C  (70°F)  to  obtain  temperature  deltas  between  entering  chilled  and  leaving  chilled  water 
temperature of 1.7°C up to 16.7°C (3°F up to 30°F). 
 

Water Quality 

-

 

The practical and economical application of liquid chillers requires that the quality of the water supply 

for the condenser and evaporator be analyzed by a water treatment specialist. Water quality may affect the performance 
of any chiller through corrosion, deposition of heat-resistant scale, sedimentation or organic growth. These will degrade 
chiller  performance  and  increase  operating  and  maintenance  costs.  Normally,  performance  may  be  maintained  by 
corrective water treatment and periodic cleaning of tubes. If water conditions exist which cannot be corrected by proper 
water  treatment,  it  may  be  necessary  to  provide  a  larger  allowance  for  fouling,  and/or  to  specify  special  materials  of 
construction. 
 

General  Piping 

-  All  chilled  water  and  condenser  water  piping  should  be  designed  and  installed  in  accordance  with 

accepted piping practice. Chilled water and condenser water pumps should be located to discharge through the chiller 
to assure positive pressure and flow through the unit. Piping should include offsets to provide flexibility and should be 
arranged to prevent drainage of water from the evaporator and condenser when the pumps are shut off. Piping should 
be adequately supported and braced independently of the chiller to avoid the imposition of strain on chiller components. 
Hangers must allow for alignment of the pipe. Isolators in the piping and in the hangers are highly desirable in achieving 
sound and vibration control. 

 

Convenience Considerations 

- To facilitate the performance of routine maintenance work, some or all of the following 

steps may be taken by the purchaser. Evaporator and condenser waterboxes are equipped with plugged vent and drain  

Содержание YZ

Страница 1: ...ENGINEERING GUIDE YORK YZ Centrifugal Chiller Form 161 01 EG1 0618 MODEL YZ MAGNETIC BEARING CENTRIFUGAL CHILLER Style A 580 through 3500 kW 165 through 1000 Tons Utilizing R 1233zd...

Страница 2: ...01 EG1 0618 2 Table of Contents Nomenclature 3 Introduction 4 Unit Components 6 Equipment Overview 8 Codes and Standards 14 Chiller Options 16 Application Data 17 Unit Weights Dimensions 22 Visit YORK...

Страница 3: ...no filter H harmonic filter VSD Cooling Product Family Motor Name Compressor Name Unit Mod Level VSD Name Motor Family Motor Size Code Motor Configuration Level Compressor Family Compressor Size Code...

Страница 4: ...ximum chiller efficiency under actual not just theoretical operating conditions Now with the YORK YZ efficiency is improved up to an impressive 7 at part load and as much as an additional 5 at full lo...

Страница 5: ...ice design principles that are consistent with our family of centrifugal chillers We made sure that this chiller and specifically the driveline was field serviceable by a single source supplier who al...

Страница 6: ...YZ Engineering Guide Form 161 01 EG1 0618 6 Unit Components Suction Line Endsheet OptiView Control Panel Condenser Sight Glass Lockout Handle Variable Speed Drive Discharge Line...

Страница 7: ...YZ Engineering Guide Form 161 01 EG1 0618 7 Unit Components Continued VSD Coolant Reservoir Refrigerant Purge Unit Compact Waterbox Evaporator Direct Drive Compressor Motor...

Страница 8: ...trol is achieved by the combined use of variable speed control and mechanical flow regulation to provide fully modulating control from maximum to minimum load For normal air conditioning applications...

Страница 9: ...and voltage of the electrical power to the motor The capacity control logic shall automatically adjust motor speed and compressor diffuser geometry for maximum part load efficiency by analyzing infor...

Страница 10: ...the OptiView control panel OPTIVIEW CONTROL CENTER Note Please refer to the YZ Operations Maintenance Manual 161 01 OM1 for a complete description of features and functionality The YORK OptiView Cont...

Страница 11: ...sheets drilled and reamed to accommodate the tubes are welded to the end of each shell Intermediate tube supports are fabricated from carbon steel plates and drilled and reamed to eliminate sharp edg...

Страница 12: ...Flow Control Refrigerant flow to the evaporator is controlled by the YORK variable orifice control system Liquid refrigerant level is continuously monitored to provide optimum subcooler condenser and...

Страница 13: ...rt Equipment by Johnson Controls allows the connection of data streams from equipment to the cloud providing unprecedented insights into operations Smart Equipment helps maximize system control for gr...

Страница 14: ...m 7 Driveline separate from split shells Shipped as four major subassemblies with refrigerant charge shipped separately This form is best used when the chiller must fit through a tight space limited b...

Страница 15: ...7012 KHK High Pressure Gas Control Law ELECTRICAL CODES c U L Underwriters Laboratory N E C National Electrical Code CE Directive 93 68 EEC IP Ingress Protection GB 5226 1 ETL Electrical Testing Labs...

Страница 16: ...psig DWP Corrosion protection None Internally epoxy coated waterboxes and tubesheets sacrificial anodes Unit Configuration Ability to isolate refrigerant charge in the condenser None Isolation valves...

Страница 17: ...ther valve while the unit is fully charged The purpose of the relief valves is to quickly relieve excess pressure of the refrigerant charge as a safety precaution in the event of an emergency such as...

Страница 18: ...many cases but do require more sophisticated control and flow monitoring YZ chillers will operate successfully in VPF systems With a minimum allowable evaporator tube velocity of 0 5m s 1 5 fps for s...

Страница 19: ...tube freeze up A flow switch is factory installed in the evaporator nozzle and connected to the OptiView panel which assures adequate chilled water flow during operation Condenser Water The chiller is...

Страница 20: ...to the desired temperature Figure 2 Series Parallel Arrangement Series Counter Flow Arrangement Chillers may be applied in pairs with chilled water circuits connected in series and with the condenser...

Страница 21: ...0 380 342 423 50 Hz 415 415 374 456 400 400 360 440 380 380 342 423 Copper Conductors Only copper conductors should be connected to compressor motors and starters Aluminum conductors have proven to be...

Страница 22: ...YZ Engineering Guide Form 161 01 EG1 0618 22 Unit Weights Dimensions B Min of 915 mm 3 ft Min of 610 mm 2 ft Service Clearance C A Min of 610 mm 2 ft D...

Страница 23: ...3314 2 9 m 9 4 2 4 m 7 9 4 3 m 14 4 3 m 14 11750kg 25900 lb FA3914 CA3314 3 1 m 10 0 2 4 m 7 9 4 3 m 14 4 3 m 14 12800 kg 28200 lb FA3916 SA3916 3 3 m 10 7 2 6 m 8 5 4 9 m 16 4 9 m 16 16050 kg 35350 l...

Страница 24: ...VE OUR NATURAL RESOURCES THINK BEFORE YOU PRINT Copyright by Johnson Controls 2017 Form 161 01 EG1 Issue Date June 2018 Supersedes 161 01 EG1 1217 Subject to change without notice ALL RIGHTS RESERVED...

Отзывы: