57
JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
TABLE 2 -
VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
PROTOCOL
BACNET MS/TP
MODBUS RTU
5
YORKTALK 2
DE MODIFIER ADDRESS
0 to 41943(3)
1
-1
DE MODIFIER OFFSET
0 to 99(4)
0
N/A
P1 PROTOCOL
BACNET
N/A
N/A
P1 MANUAL MAC ADDRESS
0-127(1)
N/A
N/A
P1 BAUD RATE
9600 To 76800 or Auto Selectable(1)
N/A
N/A
P1 PARITY
NONE
N/A
N/A
P1 STOP BITS
1
N/A
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127(1)
N/A
P2 BAUD RATE
N/A
19,200(2)
N/A
P2 PARITY
N/A
NONE(2)
N/A
P2 STOP BITS
N/A
1
N/A
P2 HW SELECT BIT
N/A
RS-485 or RS-232(1)
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
P1 HW SELECT BIT
N/A
N/A
N/A
CHILLER ID
N/A
N/A
0
1
As required by network
2
Or other as required by network
3
Number is multiplied by 100, set as required by network
4
Number is added to de modifier address, set as required by network
5
Unit operating software version C.Mmc.13.03 or later required for Modbus Protocol
Reboot required (cycle power) after set-
tings are changed.
The table below defines the real time error numbers
that may be encountered during communication setup
and a description of each.
TABLE 3 -
REAL TIME ERROR NUMBERS
ERROR
NUMBER (##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
Содержание YLPA 0115SE
Страница 4: ...4 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 10: ...10 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 16: ...16 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 26: ...26 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 30: ...30 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 72: ...72 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 79: ...79 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 YLPA P I Diagram ...
Страница 86: ...86 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 88: ...88 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...