74
JOHNSON CONTROLS
FORM 150.68-ICOM1
ISSUE DATE: 10/15/2020
OPERATING LIMITATIONS
Min. Max. Min. Max. Min. Max.
Liquid Outlet Temperature (Water)
°F
Liquid Outlet Temperature Range (
∆
T)
°F
Air Temperature - Standard Unit
°F
Liquid Outlet Temperature (Water)
°F
Liquid Outlet Temperature Range (
∆
T)
°F
Air Temperature - Standard Unit
°F
gpm
181
700
181
700
200
850
ftH
2
O
5.4
43.0
5.4
43.0
3.4
55.4
psi
psi
V
(1) Unit may operate unloaded up to 125ºFdepending on model size and site conditions.
(2) Tol/-10%
Power Supply Voltage
(2)
Heating
Mode
Maximum Refrigerant Side Pressure
Heat Exchanger Flow Rate
Maximum Water Side Pressure
Heat Exchanger Presssure Drop
14 to 95
150
650
200V 3Ø, 60Hz (nominal)
230V 3Ø, 60Hz (nominal)
380V 3Ø, 60Hz (nominal)
460V 3Ø, 60Hz (nominal)
575V 3Ø, 60Hz (nominal)
6 to 15
0170SE
0145SE
0115SE
95 to 131
YLPA
39 to 59
6 to 15
Cooling
Mode
32 to 115
(1)
psig
psig
PHYSICAL DATA
YLPA
0115SE
0145SE
0170SE
Number of refrigerant circuits
2
Refrigerant Charge
(1)
System 1 /System 2
lb
126 / 139
177 / 130
177 / 177
Oil Charge
System 1 /System 2
lb
29.5 / 29.5
44.2 / 29.5
44.2 / 44.2
Compressor
Number of compressors
2 / 2
3 / 2
3 / 3
Type
Scroll
Refrigerant to Liquid
Heat Exchanger
Number
1
Type
Shell and Tubes
Water Volume
I
250
300
Water Connections
inch
8
Ambient Coils Fans
Number of Fans (circuit 1 / circuit 2)
4 / 4
6 / 4
6 / 6
Total Air Flow - Standard Models
m
3
/s
47
58
70
Dimensions
Length
inch
194.4
230.5
274.4
Width
inch
88.4
88.4
88.4
Height
inch
94.1
94.1
94.1
Basic Unit Weight
Shipping Weight
lb
9811
11243
12124
Operating Weight
lb
10472
11904
13447
200
3.4 38.8 6.6 58.1
6.6
58.1
850
(1) Liquid sub-cooling measured at the liquid line should be between 9°F to 14°F at circuit full load
Sub-cooling is determined by the level of refrigerant charge in each system.
(2) The oil charge here includes the oil from the compressor and the extra oil added in the plant
Содержание YLPA 0115SE
Страница 4: ...4 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 10: ...10 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 16: ...16 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 26: ...26 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 30: ...30 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 72: ...72 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 79: ...79 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 YLPA P I Diagram ...
Страница 86: ...86 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 88: ...88 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...