Unit Safeties
Unit Safeties are faults that cause all running compressors
to be shut down.
UNIT FAULT:
LOW AMBIENT TEMP
The low ambient temperature cut-out is a safety shutdown
designed to protect the unit from operating in low ambient
conditions. In the cooling mode if the outdoor ambient
temperature falls below the programmable cutout, the
unit will shut down. Restart can occur when temperature
rises 0.6ºF above the cut-off. In the heating mode, if the
outdoor ambient temperature falls below 14ºF or if the
unit is fitted with the two speed option and fan speed
inhibit is in effect 18ºF, the unit will shut down. Restart
can occur when temperature rises to above 16ºF, or if
the unit is fitted with the two speed option and fan speed
inhibit is in effect at 19.6ºF.
UNIT FAULT:
HIGH AMBIENT TEMP
In the heating mode, only a high ambient temperature
cut-out is a safety shutdown designed to protect the
unit from operating in high ambient conditions. In the
heating mode, if the outside ambient temperature rises
to 77ºF the unit will shut down. Restart can occur when
temperature falls to 73.4ºF.
UNIT FAULT:
LOW LIQUID TEMP
The low leaving chilled liquid temperature cut-out is
operative in the cooling mode only. This safety protects
the unit from a water heat exchanger freeze-up should
the chilled liquid temperature drop below the freeze
point in the cooling mode. This situation could occur
under low flow conditions or if the microprocessor
setpoint values are improperly programmed. Anytime
the leaving chilled liquid temperature (water or glycol)
drops below the cut-out point, the unit will shutdown.
Restart can occur when chilled liquid temperature rises
2°F above the cut-out.
UNIT FAULT:
115VAC UNDER VOLTAGE
The under voltage safety assures that the system is
not operated at voltages where malfunction of the
microprocessor could result in system damage. When the
110 Vac to the microprocessor drops below the limit, a
unit fault is initiated to safely shut down the unit. Restart
is allowed when the 110 Vac is within limits and the
anti-recycle timers have finished counting down, unless
MANUAL POWER FAIL RESTART is programmed
under the OPTION key. In this case the unit switch must
be set to OFF then back to ON to reset this trip.
Units With Optional Hydro Kit
Units with one pump indicates the manual motor starter
protecting the pump from short circuit or overload
conditions has tripped or been set to OFF. Setting the
device to ON will reset the trip.
Units with two pumps, duty and standby indicates that
both the manual motor starters protecting the pumps
from short circuit or overload conditions have tripped
or both have been set to OFF. Setting at least one of the
devices to ON will reset the trip.
UNIT FAULT:
PUMP FAIL MAKE FLOW
Units with one pump, after the 30 second stop to start
timer has timed out the Pump is started if there is
• a Leaving Liquid Temperature Cutout, or
• any of the compressors are running or
• with the daily schedule not calling for a shutdown
with unit switch on and
• the remote stop/start input closed (terminals 13 &
51 on -XTBC1). If the flow switch does not close
within 10 seconds the unit locks out on UNIT
FAULT: PUMP FAIL MAKE FLOW and the
pump is stopped. Setting the unit switch to OFF
then back to ON will reset the trip.
Units with two pumps, duty and standby, after the 30
second stop to start timer has timed out the Pump is
started if there is a
• Leaving Liquid Temperature Cutout, or
• any of the compressors are running or with the
daily schedule not calling for a shutdown with
unit switch on and
• the remote stop/start input closed (terminals 13 &
51 on -XTBC1. If the flow switch does not close
within 10 seconds the running pump is stopped
and the standby pump is started. If in a further 10
seconds the flow switch does not close the unit
locks out on UNIT FAULT: PUMP FAIL MAKE
FLOW and the running pump is stopped. Setting
the unit switch to OFF then back to ON will reset
the trip. In attempting to clear this fault also check
that one of the manual motor starters protecting
the pumps has not tripped.
Содержание YLPA 0115SE
Страница 4: ...4 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 10: ...10 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 16: ...16 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 26: ...26 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 30: ...30 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 72: ...72 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 79: ...79 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 YLPA P I Diagram ...
Страница 86: ...86 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...
Страница 88: ...88 JOHNSON CONTROLS FORM 150 68 ICOM1 ISSUE DATE 10 15 2020 Page Left Intentionally Blank ...