JOHNSON CONTROLS
42
FORM 160.69-O2
ISSUE DATE: 9/30/2020
SECTION 6 – MAINTENANCE
REFRIGERANT CHARGING
To avoid the possibility of freezing liquid within the
evaporator tubes when charging an evacuated system,
only refrigerant vapor from the top of the cylinder
must be admitted to the system pressure until the sys-
tem pressure is raised above the point corresponding to
the freezing point of the evaporator liquid. For water,
the pressure corresponding to the freezing point is 8.54
PSIG (58.9 kPa) for R-134a (at sea level).
While charging, every precaution must be taken to pre-
vent moisture laden air from entering the system.
The charging connection should be purged each time
a full cylinder of refrigerant is connected or changed.
Refrigerant may be furnished in cylinders contain-
ing either 30, 50, 125 or 1750 lbs. (207, 345, 862, or
12,066 kg) of refrigerant.
R-134A
EVAPORATOR
CODE
LBS.
KG'S
FB
11022
5000
FC
10378
4707
FD
9725
4411
F2
11411
5176
F3
10857
4925
F4
10250
4649
GB
13485
6117
GC
12698
5760
GD
11900
5398
G2
13970
6337
G3
13292
6029
G4
12550
5693
HB
12292
5576
HC
11674
5295
HD
10875
4933
H2
12711
5766
H3
12089
5484
H4
11400
5171
KB
15057
6830
KC
14301
6487
KD
13325
6044
K2
15553
7055
K3
14793
6710
K4
13950
6328
TABLE 3 -
REFRIGERANT CHARGE
R-134A
EVAPORATOR
CODE
LBS.
KG'S
BB
7132
3235
BC
6554
2973
BD
6000
2722
B2
7144
3241
B3
6680
3030
B4
6275
2846
CB
8871
4024
CC
8446
3831
CD
8050
3651
C2
9622
4365
C3
8949
4059
C4
8450
3833
DB
8999
4082
DC
8453
3834
DD
7925
3595
D2
9327
4231
D3
8900
4037
D4
8450
3833
EB
11162
5063
EC
10496
4761
ED
9850
4468
E2
11447
5192
E3
10925
4955
E4
10375
4706
Содержание YD A
Страница 8: ...JOHNSON CONTROLS 8 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 28: ...JOHNSON CONTROLS 28 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 34: ...JOHNSON CONTROLS 34 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 48: ...JOHNSON CONTROLS 48 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...