SECTION 6 – MAINTENANCE

*One standard atmosphere  = 14.696 Psia

= 760 mm Hg. absolute pressure at 32°F

= 29.921 inches Hg. absolute at 32°F 

NOTES: PSIA = Lbs. per sq. in. gauge pressure

= Pressure above atmosphere

PSIA = Lbs. per sq. in. absolute pressure

= Sum of gauge plus atmospheric pressure

TABLE 2 - 

SYSTEM PRESSURES

* GAUGE

ABSOLUTE

BOILING

TEMPERATURES OF

WATER °F

Inches Of Mercury 

(HG) Below One

Standard Atmosphere

PSIA

Millimeters Of
Mercury (HG)

Microns

0

10.24"
22.05"
25.98"
27.95"
28.94"
29.53"
29.67"
29.72"

29.842"
29.882"
29.901"
29.917"
29.919"

29.9206"

29.921"

14.696

9.629
3.865
1.935

.968
.481
.192
.122
.099
.039
.019
.010
.002
.001
.0002

0

760.
500.
200.
100.

50.
25.
10.

6.3

5.
2.

1.0

.5
.1

.05
.01

0

760,000
500,000
200,000
100,000

50,000
25,000
10,000

6,300
5,000
2,000
1,000

500
100

50
10

0

212
192
151
124
101

78

52
40
35
15
+1

-11

-38
-50
-70

VACUUM TESTING

After the pressure test has been completed, the vacuum 

test should be conducted as follows:

1.  Connect a high capacity vacuum pump, with in-

dicator, to the system charging valve as shown in 

Figure 9 on page 39

 and start the pump. (See 

Vacuum Dehydration on page 41

.)

2.  Open wide all system valves. Be sure all valves to 

the atmosphere are closed.

3.  Operate the vacuum pump in accordance with 

VACUUM DEHYDRATION

 until a wet bulb 

temperature of +32°F or a pressure of 5 mm Hg 

is reached. See 

Table 2 on page 40

 for corre-

sponding values of pressure.

4.  To improve evacuation circulate hot water (not 

to exceed 125°F, 51.7ºC) through the evaporator 

and condenser tubes to thoroughly dehydrate the 

shells. If a source of hot water is not readily avail-

able, a portable water heater should be employed. 

DO NOT USE STEAM

. A suggested method is 

to connect a hose between the source of hot water 

under pressure and the evaporator head drain con-

nection, out the evaporator vent connection, into 

the condenser head drain and out the condenser 

vent. To avoid the possibility of causing leaks, the 

temperature should be brought up slowly so that 

the tubes and shell are heated evenly.

5.  Close the system charging valve and the stop 

valve between the vacuum indicator and the vac-

uum pump. Then disconnect the vacuum pump 

leaving the vacuum indicator in place.

6.  Hold the vacuum obtained in Step 3 in the system 

for 8 hours; the slightest rise in pressure indicates 

a leak or the presence of moisture, or both. If, after 

24 hours the wet bulb temperature in the vacuum 

indicator has not risen above 40°F (4.4°C) or a 

pressure of 6.3 mm Hg, the system may be con-

sidered tight.

Be sure the vacuum indicator is valved off 

while holding the system vacuum and be 

sure to open the valve between the vacuum 

indicator and the system when checking 

the vacuum after the 8 hour period..

7.  If the vacuum does not hold for 8 hours within the 

limits specified in Step 6 above, the leak must be 

found and repaired.

Содержание YD A

Страница 1: ...MODEL YD STYLE A B WITH OPTIVIEW CONTROL CENTER AND ELECTRO MECHANICAL STARTER COOLING ONLY CENTRIFUGAL LIQUID CHILLERS OPERATING MAINTENANCE Supersedes 160 69 O2 912 Form 160 69 O2 920 Issue Date Sep...

Страница 2: ...ls This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in...

Страница 3: ...equipment If there is any question regarding the applicability of these documents rig ging lifting and operating service personnel should verify whether the equipment has been modified and if current...

Страница 4: ...W CB 5CX DA 5DA DB 5DB DC 5DC DE 5DE DF 5DF DG 5DG DH 5DH DJ 5DJ DK 5DK DL 5DL NOMENCLATURE YD XF XA J2 CA A B or C POWERSUPPLY for 60 Hz 5 for 50 Hz DESIGN LEVEL MODEL CONDENSER CODE XA XB XC XD YA Y...

Страница 5: ...System 27 Prolonged Shutdown 27 SECTION 3 SYSTEM COMPONENTS DESCRIPTION 29 General 29 Compressor 29 Capacity Control 29 Compressor Lubrication System 29 Oil Pump 30 Oil Heater 32 Motor Driveline 32 H...

Страница 6: ...ing 45 Tube Cleaning Procedures 45 Acid Cleaning Of Tubes 46 Commercial Acid Cleaning 46 Testing For Evaporator And Condenser Tube Leaks 46 Compressor 47 Electrical Controls 47 SECTION 7 PREVENTIVE MA...

Страница 7: ...GURE 6 Schematic Drawing YD Compressor Lubrication System 31 FIGURE 7 Oil Return System 35 FIGURE 8 Charging Oil Reservoir With Oil 36 FIGURE 9 Evacuation Of Chiller 39 FIGURE 10 Saturation Curve 41 F...

Страница 8: ...JOHNSON CONTROLS 8 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 9: ...y is equipped with a potentiometer to provide vane posi tion A calibration procedure assures displayed posi tion accuracy The vanes can be manually controlled Each compressor also has a Discharge Temp...

Страница 10: ...features are detailed separately be low If equipped with the compressor Variable Geometry Diffuser VGD the chiller is started with the VGD in the fully open position Upon receipt of a chiller start s...

Страница 11: ...llow Lead motor current Meanwhile the Lead compressor Pre rotation Vanes have been modulated to maintain the Leaving Chilled Liquid Temperature setpoint unless Lag Start with High Head was performed W...

Страница 12: ...Con trol Valve while bringing on the Lead compressor It displays Lag Start when performing the Refrigerant Level Control Lag Start mode while starting the Lag compressor The Override Time Remaining d...

Страница 13: ...lowed to operate all the way up to its full load amps of 800 Amps because the total chiller current is being limited to 1120 Amps Compressor Lockout The COMPRESSOR LOCKOUT Setpoint available on the Ca...

Страница 14: ...e rotation Vanes are driven closed When the Vanes have fully closed or 210 seconds have elapsed whichever occurs first the Discharge Valve is then driven closed When the Discharge Valve has fully clos...

Страница 15: ...or Discharge Valve Electro Mechanical Starter Chiller Start Sequence Auto zero the 3 Oil Pressure Transducers Pre Lube cycle Lead Compressor Normal Sequence Extended prelube switch applies only to lea...

Страница 16: ...oint Timer Is Lag Compressor Ready to Start Yes Yes Yes NO No No Pre Lube Lag Oil Pump Don t auto zero oil pressure transducers No No 2n Trend rate of pull down on startup to decide on d compr Antirec...

Страница 17: ...ontrol Lag Compr PRVs are controlled to follow motor current of Lead System Run Two Compressors 40 Seconds Alarm Fault No Delay 50 seconds To allow motor starting transition time Are Motor Currents Eq...

Страница 18: ...Lag Compressor Discharge Valve Lag Compr Disch Valve Closed Stop Lag Compressor Motor Drive Lag Compressor vanes closed Post Lube Run Time Lag Compressor Yes No Yes 1 Compr Running Restart 2nd compr i...

Страница 19: ...lves on both compressors Stop both compressor motors Post Lube Run time both compr oil pumps Energize Oil Heater 1 Compressor Running from Page 1 or 4 Chiller normal or cycling stop signal Stop Lead c...

Страница 20: ...ult Stop manual or auto restart Stop both compressors simultaneously Chiller Fault Condition Post Lube Run time both compr oil pumps Energize Oil Heater 1 Compressor Running from Page 1 or 4 Chiller F...

Страница 21: ...ng LChWT Lag Compressor following current of Lead No Yes No Yes Close Compressor Pre rotation Vane Motors No Have of Total Surge Counts Exceeded the allowed within time period setting Stop and Lockout...

Страница 22: ...JOHNSON CONTROLS 22 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 23: ...IR Proper operating oil level During operation the oil level should fall to the Operating Range identified on the vertical oil level indicator label See Figure 3 on page 23 If the oil level during ope...

Страница 24: ...initiated and will run for 30 minutes after the compressor starts If the chiller shuts down during this period of time it cannot be started until the timer completes the 30 minute cycle 4 The chilled...

Страница 25: ...hilled water temperature Cooling tower fan cycling will normally provide adequate control of the entering condenser water temperature on most instal lations OPERATING LOG SHEET A permanent daily recor...

Страница 26: ...procedure the operator will avoid serious operating difficulty The following list of inspections and procedures should be used as a guide Daily 1 Check OptiView Control Center displays 2 If the compre...

Страница 27: ...eously with the oil pump The actual water pump con tact operation is dependent upon the position of Microboard jumper J54 3 Open the switch to the cooling tower fan motors if used 4 The compressor sum...

Страница 28: ...JOHNSON CONTROLS 28 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 29: ...ssor is able to handle the load more efficiently COMPRESSOR LUBRICATION SYSTEM The chiller lubrication system consists of the oil pump oil filter oil cooler and all interconnecting oil piping and pass...

Страница 30: ...e oil pump should operate at all times during chiller operation On shutdown of the system for any reason the oil pump operates and continues to run for 150 seconds The system cannot restart during tha...

Страница 31: ...NTROLS 31 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FORM 160 69 O2 ISSUE DATE 9 30 2020 3 LOW SPEED GEAR REAR BEARING DOUBLE BELLOWS SHAFT SEAL Figure 6 SCHEMATIC DRAWING YD COMPRESSOR LUBRICATION SYSTE...

Страница 32: ...ors or suction baffles are located above the tube bundle to prevent liquid refrig erant carryover into the compressor A 2 liquid level sight glass is located on the side of the shell to aid in determi...

Страница 33: ...the refrigerant in this system must be performed by a qualified service technician OPTIONAL HOT GAS BYPASS Hot gas bypass is optional and is used to eliminate compressor surge during light load or hig...

Страница 34: ...JOHNSON CONTROLS 34 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 35: ...To change the dehydrator use the following procedure 1 Shut the stop valves on the condenser gas line oil return line to rotor support and inlet end of the dehydrator 2 Remove the dehydrator Refer to...

Страница 36: ...il and connect the pump discharge connection to the oil charging valve A located on the remote oil reservoir cover plate See Figure 8 on page 36 Do not tighten the connection at the charging valve unt...

Страница 37: ...roblem Remove obstruction Temperature difference between leav ing chilled water and refrigerant in evaporator greater than normal with high discharge temperature Evaporator tubes dirty or restricted C...

Страница 38: ...Inspect and replace worn parts Partially blocked oil supply inlet Check oil inlet for blockage SYMPTOM OIL PRESSURE GRADUALLY DECREASES NOTED BY OBSERVATION OF DAILY LOG SHEETS When oil pump VSD frequ...

Страница 39: ...leaks too small to be found by the soap test To test with R 22 proceed as follows 1 With no pressure in the system charge R 22 gas into the system through the charging valve to a pressure of 2 PSIG 14...

Страница 40: ...pressure of 5 mm Hg is reached See Table 2 on page 40 for corre sponding values of pressure 4 To improve evacuation circulate hot water not to exceed 125 F 51 7 C through the evaporator and condenser...

Страница 41: ...n pressure tested and found to be tight prior to evacuation then the saturation tempera ture recordings should follow a curve similar to the typical saturation curve shown as Figure 10 on page 41 The...

Страница 42: ...rant is connected or changed Refrigerant may be furnished in cylinders contain ing either 30 50 125 or 1750 lbs 207 345 862 or 12 066 kg of refrigerant R 134A EVAPORATOR CODE LBS KG S FB 11022 5000 FC...

Страница 43: ...rigerant level should be observed and the level re corded after initial charging HANDLING REFRIGERANT FOR DISMANTLING AND REPAIRS If it becomes necessary to open any part of the refriger ant system fo...

Страница 44: ...RM 160 69 O2 ISSUE DATE 9 30 2020 SECTION 6 MAINTENANCE LD00476 Figure 12 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES Minimum Insulation Resistance vs Temperature per IEEE Std 43 Open Motors...

Страница 45: ...radual drop off in cooling capacity can also be caused by a gradual leak of refrigerant from the system or by a combination of fouled tubes and shortage of refrigerant charge An excessive quantity of...

Страница 46: ...ten at each section of tubes for a hissing sound that would indicate gas leakage This will assist in locating the section of tubes to be further investigated If the probable location of the leaky tube...

Страница 47: ...passages or dirty oil fil ters If the unit is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the presence of aluminu...

Страница 48: ...JOHNSON CONTROLS 48 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 49: ...tion Grease fittings are not supplied and bearings are designed for long life under standard conditions Frames 284T thru 587UZ are furnished with double shielded or open ball or roller bearings It is...

Страница 50: ...e to the benefit of the user to provide for proper water treatment to provide for a longer and more economical life of the equipment The following recommendation should be followed in determining the...

Страница 51: ...lsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 5 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effec...

Страница 52: ...ennsylvania USA 17349 1 800 524 1330 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 69 O2 920 Issue Date Septem...

Отзывы: