
JOHNSON CONTROLS
26
FORM 160.69-O2
ISSUE DATE: 9/30/2020
SECTION 2 – SYSTEM OPERATING PROCEDURES
Monthly
Leak check the entire chiller.
Quarterly
Perform chemical analysis of oil.
Semi-Annually (or more often as required)
1.
Change and inspect compressor oil filter element.
2. Oil return system.
a. Change dehydrator.
b. Check nozzle of eductor for foreign particles.
3. Check controls and safety cutouts.
Annually (more often if necessary)
If quarterly inspection indicates oil is fine,
replacing the oil is not necessary.
1. Drain and replace the oil in the compressor oil
sump. (See “Oil Charging Procedure”)
2. Evaporator and Condenser.
a. Inspect and clean water strainers.
b. Inspect and clean tubes as required.
c. Inspect end sheets.
3. Compressor Drive Motor (See motor manufactur-
ers maintenance and service instruction supplied
with unit)
a. Clean air passages and windings per manu-
facturers instructions.
b. Meg motor windings – See
Figure 11 on
page 26
for details.
c. Lubricate per motor manufacturer recom-
mendations.
4. Inspect and service electrical components as neces-
sary.
5. Perform refrigerant analysis.
OPERATING INSPECTIONS
By following a regular inspection using the display
readings of the Microcomputer Control Center, and
maintenance procedure, the operator will avoid serious
operating difficulty. The following list of inspections
and procedures should be used as a guide.
Daily
1. Check OptiView™ Control Center displays.
2. If the compressor is in operation, check the bear-
ing oil pressure on the
SYSTEM
Screen. Also
check the oil level in the oil reservoir. Operating
oil level should be operating range of oil indicator.
Drain or add oil if necessary.
3. Check entering and leaving condenser water pres-
sure and temperatures for comparison with job
design conditions. Condenser water temperatures
can be checked on the
SYSTEM
Screen.
4. Check the entering and leaving chilled liquid tem-
peratures and evaporator pressure for compari-
son with job design conditions on the
SYSTEM
Screen.
5. Check the condenser saturation temperature
(based upon condenser pressure sensed by the
condenser transducer) on the
SYSTEM
Screen.
6. Check the compressor discharge temperature on
the
SYSTEM
Screen. During normal operation
discharge temperature should not exceed 220°F
(104°C).
7. Check the compressor motor current on the
SYS-
TEM
Screen.
8. Check for any signs of dirty or fouled condenser
tubes. (The temperature difference between water
leaving condenser and saturated condensing tem-
perature should not exceed the difference record
-
ed for a new unit by more than 4°F, 2.2°C).
Weekly
Check the refrigerant charge. (See
Содержание YD A
Страница 8: ...JOHNSON CONTROLS 8 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 22: ...JOHNSON CONTROLS 22 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 28: ...JOHNSON CONTROLS 28 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 34: ...JOHNSON CONTROLS 34 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 48: ...JOHNSON CONTROLS 48 FORM 160 69 O2 ISSUE DATE 9 30 2020 THIS PAGE INTENTIONALLY LEFT BLANK...