FORM 150.60-NM3
7
YORK INTERNATIONAL
OPERATIONAL LIMITATIONS
LD02160
CODE
MODEL
E
YCAZ88EE8
YCAJ44HE8
YCAJ54HE8
H
YCAJ55HE8
YCAJ65HE8
FIG. 2
COOLER WATER PRESSURE DROP
VOLTAGE LIMITATIONS
The following voltage limitations are absolute and opera-
tion beyond these limitations may cause serious dam-
age to the compressor.
VOLTAGES
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
380/415-3-50
342
440
346-3-50
311
381
575-3-60
517
633
NOTES:
1. Units can be used for brine temperatures between 15°F and
39°F by resetting standard controls.
2. Operation below 25°F requires the Optional Low Ambient kit.
(Minimum recommended operating temperature is 0°F).
3. Operation above 115°F requires Optional High Ambient kit. (Maxi-
mum recommended operating temperature is 130°F).
4. The evaporator is protected against freeze-up to -20°F with an
electrical heater cable standard.
CAUTION: Excessive flow will cause damage to the
cooler. Do not exceed maximum cooler
GPM. Special care should be taken when
multiple chillers are fed by a single pump.
TEMPERATURES AND FLOWS
MODEL
LVG. LIQUID
COOLER
AIR ON
YCA
TEMP. °F
GPM
COND. - °F
Min.
1
Max.
Min.
Max. Min.
2
Max.
3
Z88EE8
40
50
120
580
0
130
J44HE8
40
50
150
640
0
130
J54HE8
40
50
120
640
0
130
J55HE8
40
50
150
640
0
130
J65HE8
40
50
150
640
0
130
Содержание YCAZ88EE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM ...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166 ...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171 ...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172 ...