FORM 150.60-NM3
77
YORK INTERNATIONAL
2. When discharge pressure reaches 320 PSIG fan 1
(SYS 1, 7M) or fan 3 (SYS 2, 10M) will be energized
in the reverse direction. These fans will remain ener-
gized until discharge pressure drops below 120
PSIG.
3. If discharge pressure reaches 340 PSIG, the revers-
ing fans on the respective system will be turned off.
At the same time, fan 2 (SYS 1, 6M) or fan 4 (SYS 2,
9M) will energize. This fan will remain on until dis-
charge pressure drops below 120 PSIG.
4. If discharge pressure reaches 360 PSIG and run
time has exceeded 30 seconds, fan 1 (SYS 1, EM)
or fan 3 (SYS 2, 8M) will energize turning the fan in
the forward direction. This fan will remain on until
discharge pressure drops to 140 PSIG.
Table 2 shows the operation of both modes of fan control
previously discussed.
HOT GAS BYPASS (LOADMINDER) OPTION
General
The Hot Gas Bypass Option is available as a factory
installed option to prevent compressor cycling and water
temperature fluctuation at low load. This is ac-
complished by providing further capacity reduction below
the last step of compressor cylinder unloading by intro-
ducing an artificial load to the cooler, which keeps the
compressor on the line. The option will provide hot gas
bypass on both compressors enabling hot gas to be ac-
tive regardless of which compressor is in the lead.
NOTE: The microprocessor will only activate the hot
gas on the lead compressor.
The hot gas bypass consists of a pilot operated regu-
lating valve with an integral solenoid. The pilot operated
solenoid is controlled by the microprocessor according
TABLE 2
LOW AMBIENT FAN CYCLING
CONTROL BY
CONTROL BY
TEMPERATURE & PRESSURE
PRESSURE ONLY
SYS
FAN
CONTACTOR
BELOW 25°F PRESSURE
ABOVE 25°F TEMPERATURE
TEMPERATURE
CONTROL ONLY
CONTROL ONLY
HAS NO EFFECT
ON
OFF
ON
OFF
ON
OFF
1 REV
7M
320 PSIG
120 PSIG
Will Not Start
35°F or
320 PSIG
120 PSIG
Above 25°F
340 PSIG
Turns OFF by
1
2
6M
340 PSIG
120 PSIG
25°F
Pressure
340 PSIG
120 PSIG
Only at
120 PSIG
1 FWD
5M
360 PSIG
140 PSIG
45°F
40°F
360 PSIG
140 PSIG
3 REV
10M
320 PSIG
120 PSIG
Will Not Start
35°F or
320 PSIG
120 PSIG
Above 25°F
340 PSIG
Turns OFF by
2
4
9M
340 PSIG
120 PSIG
25°F
Pressure
320 PSIG
120 PSIG
Only at
120 PSIG
3 FWD
8M
360 PSIG
140 PSIG
45°F
40°F
360 PSIG
140 PSIG
NOTE: Fans with reversing contactors will have the reversing contactors mechanically locked out when the fans are running forward. The
forward contactor will also be locked out when the fans are running in reverse.
Содержание YCAZ88EE8
Страница 16: ...16 YORK INTERNATIONAL WIRING DIAGRAMS LD02165 FIG 5 ELEMENTARY DIAGRAM ...
Страница 17: ...FORM 150 60 NM3 17 YORK INTERNATIONAL FIG 5 ELEMENTARY DIAGRAM Cont d LD02166 ...
Страница 20: ...20 YORK INTERNATIONAL CONNECTION DIAGRAM ELECTRICAL BOX FIG 7 CONNECTION DIAGRAM LD02171 ...
Страница 21: ...FORM 150 60 NM3 21 YORK INTERNATIONAL FIG 7 CONNECTION DIAGRAM Cont d LD02172 ...