Another anti-recycle timer is started each time the sys-
tems number one compressor cycles off. This anti-re-
cycle time is fixed at 120 seconds and starts to count-
down when the systems number one compressor cycles
off.
The anti-recycle message is displayed when the sys-
tem is unable to start due to either of the anti-recycle
timers being active (counting down). The actual time
displayed will be the longer of the two timers, start-to-
start or stop-to-start.
The Fan Control On Pressure is the programmed pres-
sure value that is used to stage the condenser fans on,
in relation to discharge pressure. Refer to Condenser
Fan Control in the UNIT OPERATION section and
Tables 38, 39, and 40, 41.
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION
section and Tables 38, 39 and 40, 41.
The TOTAL NUMBER OF COMPRESSORS are the
amount of compressors in the chiller, and determines
the stages of cooling available. Notice in Table 29 the
chiller is a single or dual refrigerant circuit.
This must be programmed correctly to
assure proper chiller operation.
T O T A L
N U M B E R
O F
C O M P R E S S O R S
=
6
F A N
C O N T R O L
O N
P R E S S U R E = X X X P S I G
F A N
D I F F E R E N T I A L
O F F
P R E S S U R E = X X X P S I G
TABLE 29 – PROGRAM KEY LIMITS AND DEFAULTS
PROGRAM VALUE
MODEL
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
—
200 PSIG
399 PSIG
395 PSIG
13.8 BARS
27.5 BARS
27.2 BARS
SUCTION PRESSURE CUTOUT
WATER COOLING
44.0 PSIG
70.0 PSIG
44.0 PSIG
3.03 BARS
4.83 BARS
3.03 BARS
GLYCOL COOLING
20.0 PSIG
70.0 PSIG
44.0 PSIG
1.38 BARS
4.83 BARS
3.03 BAR
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
LEAVING CHILLED LIQUID
WATER COOLING
—
—
36°F
2.2°C
TEMP. CUTOUT
GLYCOL COOLING
8.0°F
36.0°F
36.0°F
-13.3°C
2.2°C
2.2°C
ANTI-RECYCLE TIMER
—
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON-PRESSURE
—
225 PSIG
300 PSIG
230 PSIG
15.5 BARS
20.7 BARS
15.9 BARS
FAN DIFFERENTIAL OFF-PRESSURE
—
50 PSIG
150 PSIG
80 PSIG
3.45 BARS
10.3 BARS
5.52 BARS
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
TWO SYSTEMS
4
6
6
2
Содержание YCAL0080SC
Страница 112: ...YORK INTERNATIONAL 112 ELEMENTARY DIAGRAM YCAL0014SC YCAL0030SC FIG 11 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 114: ...YORK INTERNATIONAL 114 ELEMENTARY DIAGRAM YCAL0014SC YCAL0030SC LD03532 FIG 12 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 115: ...YORK INTERNATIONAL 115 FORM 150 62 NM1 This page intentionally left blank 4...
Страница 116: ...YORK INTERNATIONAL 116 ELEMENTARY DIAGRAM YCAL0034SC FIG 13 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 117: ...YORK INTERNATIONAL 117 FORM 150 62 NM1 FIG 13 ELEMENTARY DIAGRAM Cont d LD03533 ELEMENTARY DIAGRAM YCAL0034SC 4...
Страница 118: ...YORK INTERNATIONAL 118 FIG 14 ELEMENTARY DIAGRAM ELEMENTARY DIAGRAM YCAL0034SC LD03534 Wiring Diagrams...
Страница 119: ...YORK INTERNATIONAL 119 FORM 150 62 NM1 This page intentionally left blank 4...
Страница 120: ...YORK INTERNATIONAL 120 ELEMENTARY DIAGRAM YCAL0040SC YCAL0060SC FIG 15 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 122: ...YORK INTERNATIONAL 122 ELEMENTARY DIAGRAM YCAL0040SC YCAL0060SC FIG 16 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 124: ...YORK INTERNATIONAL 124 ELEMENTARY DIAGRAM YCAL0064SC YCAL0080SC FIG 17 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 126: ...YORK INTERNATIONAL 126 ELEMENTARY DIAGRAM YCAL0064SC YCAL0080SC FIG 18 ELEMENTARY DIAGRAM Wiring Diagrams...
Страница 130: ...APPENDIX 1 DIMENSIONS FIG 19 TYPE CP 1 FIG 20 TYPE CP 2 LD03839 LD03840 Appendix 1 Isolators...
Страница 135: ...YORK INTERNATIONAL 135 FORM 150 62 NM1 This page intentionally left blank...