![York YCAL0019 Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/york/ycal0019/ycal0019_installation-operation-and-maintenance-manual_4084434047.webp)
47
JOHNSON CONTROLS
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
55
OPERATIONAL LIMITATIONS (ENGLISH)
Voltage Limitations
The following voltage limitations are absolute and operation beyond these limitations may cause serious damage
to the compressor.
Excessive flow will cause damage to the cooler. Do not exceed max. cooler flow. Special
care should be taken when multiple chillers are fed by a single pump.
NOTES:
1. For leaving brine temperature below 40 °F (4.4 °C), contact your nearest Johnson Controls Office for application requirements.
2. For leaving water temperature higher than 55 °F (12.8 °C), contact the nearest Johnson Controls Office for application guidelines.
3. The evaporator is protected against freezing to -20 °F (-28.8 °C) with an electric heater as standard.
4. For operation at temperatures below 25 °F (-3.9 °C), the optional Low Ambient Kit will need to be installed on the system
(for YCAL0043 to YCAL0065).
5. For operation at temperatures above 115 °F (46.1 °C), the optional High Ambient Kit will need to be installed on the system.
TABLE 1 -
TEMPERATURES AND FLOWS
ENGLISH
YCAL
LEAVING WATER
TEMPERATURE ( °F)
COOLER FLOW (GPM)
AIR ON CONDENSER ( °F)
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
0019
40
55
17
68
0
125
0022
40
55
21
84
0
125
0028
40
55
30
150
0
125
0033
40
55
34
150
0
125
0043
40
55
40
200
0
125
0046
40
55
40
200
0
125
0052
40
55
40
300
0
125
0056
40
55
60
300
0
125
0066
40
55
60
300
0
125
TABLE 2 -
VOLTAGE LIMITATIONS
UNIT POWER
MINIMUM
MAXIMUM
200-3-60
180
220
230-3-60
207
253
380-3-60
355
415
460-3-60
414
506
575-3-60
517
633
SECTION 5 – TECHNICAL DATA
Содержание YCAL0019
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Страница 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Страница 127: ...127 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5 DIMENSIONS YCAL0052 SI CONT D...
Страница 129: ...129 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5 DIMENSIONS YCAL0056 SI CONT D...
Страница 191: ...191 JOHNSON CONTROLS SECTION 8 UNIT OPERATION FORM 150 67 NM1 ISSUE DATE 4 28 2017 8 Figure 48 WIRING LD11799A...
Страница 202: ...JOHNSON CONTROLS 202 FORM 150 67 NM1 ISSUE DATE 4 28 2017 SECTION 8 UNIT OPERATION THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...