JOHNSON CONTROLS
54
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TEChNICAl DATA
It is possible that multiple sources of power can be supplying the unit power panel. To pre
vent serious injury or death, the technician should verify that NO LETHAL VOLTAGES
are present inside the panel AFTER disconnecting power, before working on equipment.
The unit evaporator heater uses 120 VAC. Disconnecting 120 VAC power from the unit, at
or below freezing temperatures, can result in damage to the evaporator and unit as a result
of the chilled liquid freezing.
ELECTRICAL DATA
TABLE 11 – MICRO PANEL POWER SUPPLY
VOLTAGE RANGE
VOLTAGE CODE
UNIT POWER
MIN.
MAX.
-17
200-3-60
180
220
-28
230-3-60
207
253
-40
380/415-3-60
342
440
-46
460-3-60
414
506
-50
380/415-3-50
342
440
-58
575-3-60
517
633
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC SW
MIN
MAX
MODELS w/o
CONTROL
TRANS
115-1-60/50
15A
10A
15A
30 A / 240V
MODELS w/
CONTROL
TRANS
-17
200-1-60
15A
10A
15A
30 A / 240V
-28
230-1-60
15A
10A
15A
30 A / 240V
-40
380-1-60
15A
10A
15A
30 A / 480V
-46
460-1-60
15A
10A
15A
30 A / 480V
-50
380/415-1-60
15A
10A
15A
30A / 415V
-58
575-1-60
15A
10A
15A
30 A / 600V
A. Minimum #14 AWG, 75
°
C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
TABLE 12 – VOLTAGE RANGE
Содержание YCAL0012EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...