JOHNSON CONTROLS
74
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 6 - TEChNICAl DATA
lD11819
DIMENSIONS - YCAL0027 (ENGLISH)
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. yORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6';
rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'. No
more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".
44 5/16"
BASE WIDTH
50 1/16"
49 1/4"
6 3/4"
3 1/4"
3 15/16"
LEFT END
BOTTOM OF PANEL
7/8" TYP.
VIEW B-B
POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK
19"
10 3/4"
8 1/2"
2" VICTAULIC CONN
(typ)
B
B
15 1/2"
TO ACCESS PANEL 13 3/8"
2 1/4"
8 5/16"
12 13/16"
8 5/16"
12 13/16"
2" DIA
(2) 3.0 X 1.50
RIGGING HOLES
BOTH ENDS
Содержание YCAL0012EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...