JOHNSON CONTROLS
132
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - UNIT OPERATION
TABLE 20 – YCAL0012 – YCAL0032 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
TABLE 19 – YCAL0012 – YCAL0032 CONDENSER FAN CONTROL USING OUTDOOR AMBIENT
TEMPERATURE AND DISCHARGE PRESSURE (DISCHARGE PRESSURE CONTROLS WILL
NOT FUNCTION AND FAN CONTROL WILL BE BASED ON AMBIENT TEMPERATURES ONLY,
UNLESS THE OPTIONAL DISCHARGE PRESSURE TRANSDUCER IS INSTALLED).
lD12211
STANDARD CONDENSER FAN CONTROL - YCAL0012 – YCAL0032
FAN
STAGE
ON
OFF
CONTACTOR
MICROBOARD
OUTPUT
FAN #
1
OAT > 25°F (-3.9°C)
or
DP> Fan Ctrl On
Press
OAT < 20°F (6.7°C)
and
DP < Fan Ctrl On
Press - (Diff. Press)
7M
TB7-9
3
2
OAT > 65°F (18.3°C)
or
DP > Fan Ctrl On
Press
+75 psig (5.17 bar)
OAT < 60°F (15.6°C)
and
DP < Fan Ctrl On
Press -
(Diff. Press + 75 psig
(5.17 bar))
7M
&
8M
TB7-9
&
TB7-10
1
&
3
FAN
STAGE
ON
OFF
CONTACTOR
MICROBOARD
OUTPUT
FAN #
1
DP > Fan Ctrl
On Press
DP < Fan Ctrl On
Press - (Diff. Press.)
7M
TB7-9
3
2
DP > Fan Ctrl On
Press +
75 psig (5.17 bar)
DP < Fan Ctrl On
Press - ((Diff. Press.)
+ 75 psig
(5.17 bar))
7M
&
8M
TB7-9
&
TB7-10
1
&
3
FAN #1
FAN #2
Содержание YCAL0012EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...