FORM 150.66-NM2
ISSUE DATE: 09/25/2020
109
JOHNSON CONTROLS
SECTION 7 - UNIT CONTROlS
7
If the micro is programmed for CURRENT FEEDBACK
ONE PER UNIT under the OPTIONS Key, the display
will show up as the first display prior to the SYS 1
displays. Total chiller current is displayed as shown
below:
If the micro is programmed for CURRENT FEEDBACK
NONE, no current display will appear.
E V A P P U M P I S O N
E V A P H E A T E R I S O F F
S Y S 1 R U N T I M E
X X - X X - X X - X X D - H - M - S
S Y S 1 C O M P S T A T U S
1 = X X X 2 = X X X 3 = X X X
S Y S 1 L L S V I S O N
H O T G A S S O L I S O F F
S Y S 1 A M P S = 3 6 . 0
V O L T S = 0 . 8
This display indicates the status of the evaporator pump
contacts and the evaporator heater.
The evaporator pump dry contacts are energized when
any compressor is running, or the unit is not OFF on
the daily schedule and the unit switch is on, or the unit
has shutdown on a Low Leaving Chilled Liquid fault.
However, even if one of above is true, the pump will not
run if the micro panel has been powered up for less than
30 seconds or if the pump has run in the last 30 seconds
to prevent pump motor overheating.
The evaporator heater is controlled by ambient air tem-
perature. When the ambient temperature drops below
40°F the heater is turned on. When the temperature rises
above 45°F the heater is turned off. An under voltage
condition will keep the heater off until full voltage is
restored to the system.
There are several types of remote systems that can
be used to control or monitor the unit. The following
messages indicate the type of remote control mode
active:
NONE – no remote control active. Remote monitoring
may be via ISN.
ISN – YORK Talk via ISN allows remote load limiting
and temperature reset through an ISN system.
*LOAD LIM – load limiting enabled. Can be either
stage 1 or stage 2 of limiting.
*PWM TEMP – EMS-PWM temperature reset
*
Refer to SECTION 7 - UNIT CONTROLS.
The preceding five messages will appear sequentially,
first for system 1, then for system 2.
The first message indicates the system and the associated
compressors which are running.
The second message indicates the system run time in
days – hours – minutes – seconds. Please note that this
is not accumulated run time but pertains only to the
current system cycle.
The third message indicates the system, and whether the
liquid line solenoid or EEV pilot solenoid and hot gas
solenoid are being turned on by the microboard.
The fourth message indicates what stage of condenser
fan operation is active.
A C T I V E R E M O T E C T R L
N
O
N E
U N I T A M P S = 5 4 . 0
V O L T S = 1 . 2
S Y S 1 F A N S T A G E 3
Содержание YCAL0012EC
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...