JOHNSON CONTROLS
27
SECTION 5 – CYCLING SHUTDOWNS
FORM 160.00-O2
ISSUE DATE: 04/30/2019
5
shutdown will occur. This shutdown is disabled for the
first 20 seconds of the starter run, to prevent nuisance
shutdowns from heavily loaded transformers. The
voltage range is programmed on the OptiView Control
Center. If no voltage range is programmed, then this
shutdown will be disabled (ASSOCIATED LITERA-
TURE listed on Page 3).
The shutdown message displayed will be
“LCSSS -
LOW SUPPLY LINE VOLTAGE”
.
Possible Problems
• Verify that the proper voltage range is selected on
the OptiView Control Center.
• Verify proper line voltage is being applied to the
starter.
• If the problem occurs during generator operation,
add some standby load to the generator so that
the generator can respond more quickly to load
changes.
PHASE LOCKED LOOP
The cathode connection of the negative SCRs is con-
nected to the 3-phase AC power line. This informa-
tion is sent to the Logic/Trigger Board, where a circuit
generates a waveform that is synchronized to the ‘A’
phase voltage. This waveform and the ‘A’ phase volt-
age are compared, and the deviation is used to generate
an error signal. The error signal is then used to correct
the waveform and maintain synchronization with the
‘A’ phase voltage. The synchronized waveform is used
for the firing control of all the SCRs. If the error sig-
nal becomes too large then the synchronization with
the ‘A’ phase voltage will be lost. If synchronization
is not maintained, the SCRs will misfire and damage
the chiller.
The shutdown message displayed will be
“LCSSS -
PHASE LOCKED LOOP”
.
Possible Problems
• Although this circuit is very fast, storms or power
problems can cause the frequency of the ‘A’ phase
voltage to change too rapidly.
• If the problem occurs during generator operation,
ensure that the JP1 jumper has been cut (on Rev
C. or earlier Logic/Trigger Boards).
• If the problem occurs during generator operation,
add some standby load to the generator so that the
generator responds more quickly to load changes.
PHASE LOSS
The three phases of input line voltage are fed back
to the Logic/Trigger Board via the cathode connec-
tions of the negative SCRs. The RMS voltage is then
compared against a threshold value, that is 30% of the
programmed input voltage range. For example, if the
programmed input voltage range is 440-480 VAC, then
the threshold value will be 132 VAC. If the voltage
range is disabled in the OptiView Control Center then
the shutdown value will be 30% of 200 VAC. Thus,
the threshold value will be 60 VAC. Anytime one of
the three phases of input line voltage drops below the
threshold value, a Cycling shutdown will occur.
The shutdown message displayed will be
“LCSSS -
PHASE LOSS”
.
TABLE 6 -
LOW SUPPLY LINE VOLTAGE
VOLTAGE RANGE
HIGH SUPPLY LIMIT – STOPPED
HIGH SUPPLY LIMIT – RUNNING
Disabled
None
None
200 - 208
174
160
220 - 240
200
185
380
331
305
400
349
320
415
362
335
440 - 480
400
370
550 - 600
502
460
Содержание SSS 14L-B
Страница 4: ...JOHNSON CONTROLS 4 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 30: ...JOHNSON CONTROLS 30 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...