JOHNSON CONTROLS
20
FORM 160.00-O2
ISSUE DATE: 04/30/2019
SECTION 3 – LOGIC/TRIGGER BOARD
FIGURE 7 -
LOGIC/TRIGGER BOARD PIN LOCATION DIAGRAM
LD05282
RED
RED
RED
RED
RED
RED
WHT
WHT
WHT
WHT
WHT
WHT
PHASE C
PHASE B
PHASE A
J11
J10
J9
J8
J7
J6
J12
J2
J3
J4
TB1
TB2
J1
J5
1
2
12
11
10
9
8
7
6
5
4
3
2
1
1 2
3
4 5
1 2
3
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
JUMPER
DESCRIPTION
J11-PINS
J11-1
Phase “C” Negative SCR gate output. .55-2 VDC as measured to J11-2 when the starter is running.
J11-2
Phase “C” Negative SCR cathode. See J11-1.
J12-PINS
J12-1
Switched 115 VAC to cooling loop water pump motor, 115 VAC when pump is commanded to run. 0 VAC when
commanded to stop. Measured to J5-1.
J12-2
115 VAC as measured to J5-1.
TB1 PINS
TB1-1, 16
Stop Contact between the LCSSS and the OptiView Control Center.
Measure 115 VAC to J5-2 when no faults are active. Measure 0 VAC to J5-2 when faults are active.
TB1-2, 53
115 VAC supply voltage from the OptiView Control Center for the Stop Contact.
Measure 115 VAC to J5-2 whenever power is applied.
TB1-3, 24
Run / Stop connections from the OptiView Control Center.
Measure 115 VAC to J5-2 when in a run condition. Measure 0 VAC to J5-2 when in a stop condition.
TB2 PINS
TB2-1
The transmit line for the Serial Communications Link from the Micro Board in the OptiView Control Center J15-1.
TB2-2
The receive line for the Serial Communications Link from the Micro Board in the OptiView Control Center J15-2.
TB2-3
The ground line for the Serial Communications Link from the Micro Board in the OptiView Control Center J15-3.
TB2-4
The 24 VDC power supply. Connected to J30 / P30 Pin 12. Refer to the
for the proper connection on the J2 connector of the power supply. Measure 24 VDC to TB2-5.
TB2-5
The ground connection for the power supply. Connected to J30 / P30 Pin 6, and J2 Pin 6 on the power supply
inside the OptiView Control Center.
All measurements made to GND (J3-1) unless otherwise noted.
TABLE 4 -
LOGIC/TRIGGER BOARD INPUTS AND OUTPUTS
Содержание SSS 14L-B
Страница 4: ...JOHNSON CONTROLS 4 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 8: ...JOHNSON CONTROLS 8 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 24: ...JOHNSON CONTROLS 24 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 30: ...JOHNSON CONTROLS 30 FORM 160 00 O2 ISSUE DATE 04 30 2019 THIS PAGE INTENTIONALLY LEFT BLANK...