50
YORK INTERNATIONAL
PAGE 18
16
CLOSE CYCLING STATUS
CONTACTS TB4-40/41
DE-ENERGIZE 1R RELAY TO
CLOSE STEAM/HOT WATER
SHUTOFF VALVE
START 6 MINUTE
DILUTION CYCLE TIMER
ENTER DILUTION CYCLE
@ PAGE 35
8
EXIT DILUTION CYCLE
@ PAGE 42
*
STEAM
UNIT
DE-ENERGIZE 6 SOL TO CLOSE
STEAM CONDENSATE DRAIN VALVE
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
NO
YES
6 MIN.
DILUTION
TIMER
ELAPSED
➤
NO
YES
TB2-13
CLOSED
OPEN CYCLING
STATUS CONTACTS
TB4-40/41
➤
➤
NO
YES
➤
2
PAGE 11
OUT
TERMINATE DILUTION –
SHUTDOWN ALL PUMPS
➤
TERMINATE DILUTION –
SHUTDOWN ALL PUMPS
EXCEPT CHILLED
WATER PUMP
CHECK MICRO BOARD
PROGRAM JUMPER J54
➤
➤
➤
YES
NO
➤