YORK INTERNATIONAL
21
FORM 155.16-O3
A
< 33°F
(0.5°C)
CHECK CHILLED WATER
FLOW SWITCH @ TB2-12
SAFETY SHUTDOWN-DISPLAY
“DAY-TIME-LOW REFRIGERANT
TEMP-ANALOG” AS STATUS
20
PAGE 56
TRIPPED
DISPLAY
“WARNING-FAULTY
STRONG SOLN TEMP
SENSOR”
CLOSE ALARM CONTACTS
TB4-89/90 TO SOUND
AUDIBLE ALARM UNTIL
RESET WITH
“WARNING RESET KEY”
> 91°F
(32.8°C)
< 91°F
(32.8°C)
FOR 1
MINUTE
CHECK STRONG
SOLUTION TEMP
@ RT3
CLEAR “FAULTY STRONG
SOLN TEMP SENSOR”
WARNING MESSAGE WHEN
WARNING RESET KEY IS
PRESSED IN SERVICE MODE
STRONG
SOLN TEMP
SENSOR
WARNING
IN EFFECT
UNIT
RUNNING
30 MIN
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
23
PAGE 59
SAFETY SHUTDOWN-DISPLAY
“DAY-TIME-CHILLED WATER
FLOW SWITCH” AS STATUS
➤
➤
A
B
YES