YORK INTERNATIONAL
FORM 150.63-NM1
137
ANALOG INPUTS – Pressure
Refer to the unit wiring diagram. Pressure inputs are
connected to the microboard on plugs J4 and J7. These
analog inputs represent varying DC signals correspond-
ing to varying pressures. All voltages are in reference
to the unit case (ground).
System 1 discharge and suction pressures will be con-
nected to J4 of the microboard. System 2 discharge and
suction pressure transducers will be connected to J7 of
the microboard.
The discharge transducers are optional on all units. If
the discharge transducers are not installed, no connec-
tions are made to the microboard and the discharge pres-
sure readout on the display would be zero.
The suction pressure transducers are optional on
YCUL0016 - YCUL0066. If the suction transducers are
not installed, a mechanical low pressure switch will be
installed in its place, and the suction pressure readout
on the display will be 0 PSIG when the LP switch is
open, and 200 PSIG (13.79 BARG) when the LP switch
is closed.
The discharge transducers have a range from 0 to 400
PSIG. The output will be linear from .5 VDC to 4.5
VDC over the 400 PSIG (27.5 BARG) range. Table 32
shows the formula that can be used to verify the volt-
age output of the transducer. All voltage reading are in
reference to ground (unit case).
V = (Pressure in PSIG x .01) + .5
or
V = (Pressure in BARG x .145) + .5
where V = DC voltage output
Pressure = pressure sensed by transducer
The microboard connections for the Discharge Trans-
ducers:
System 1 Discharge Transducer
J4-7 = +5 VDC regulated supply to transducer.
J4-12 = VDC input signal to the microboard. See
Table 32 for voltage readings that corre-
spond to specific discharge pressures.
J4-8 = +5 VDC return
J4-9 = Drain (shield connection = 0 VDC)
System 2 Discharge Transducer
J7-7 = +5 VDC regulated supply to transducer.
J7-12 = VDC input signal to the microboard. See
Table 32 for voltage readings that corre-
spond to specific discharge pressures.
J7-8 = +5 VDC return
J7-9 = Drain (shield connection = 0 VDC)
TABLE 32 – DISCHARGE PRESSURE TRANS-
DUCER PRESSURE TO VOLTAGE
CONVERSION FORMULA
4
Содержание MILLENNIUM YCUL0016SC
Страница 35: ...YORK INTERNATIONAL FORM 150 63 NM1 35 This page is intentionally left blank 1 ...
Страница 151: ...YORK INTERNATIONAL FORM 150 63 NM1 151 This page is intentionally left blank 5 ...
Страница 152: ...YORK INTERNATIONAL 152 FIG 17 ELEMENTARY DIAGRAM MODELYCUL0040 ELEMENTARY DIAGRAM YCUL0040 Elementary Diagrams ...
Страница 155: ...YORK INTERNATIONAL FORM 150 63 NM1 155 This page is intentionally left blank 5 ...
Страница 159: ...YORK INTERNATIONAL FORM 150 63 NM1 159 This page is intentionally left blank 5 ...
Страница 163: ...YORK INTERNATIONAL FORM 150 63 NM1 163 This page is intentionally left blank 5 ...
Страница 170: ...YORK INTERNATIONAL 170 ...