FORM 201.10-NM1
79
YORK INTERNATIONAL
Operating Hours
Start Counter
Accumulated running hours and starts on each
compressor is displayed. The hours counter for an
individual system count to a total of 99,999 hours before
rollover. A total of 99,999 starts can be logged on a
system before the start counter will rollover.
The numbers “1” and “2” on the display indicate
compressor #1 and compressor #2.
These counters are zeroed at the factory, but may
indicate run time and number of starts logged during
factory testing prior to shipment.
Options
The OPTIONS key provides a display of options which
have been selected by the user. These options are
selected by the S1 Dip Switch on the Microprocessor
Board (Fig. 22). Proper programming of the switch is
important during the commissioning of the chiller. The
OPTIONS display allows a means of verifying the Dip
Switch positions without looking at or handling the
Microprocessor Board. It also eliminates visual
inspection of the sometimes difficult to determine Dip
Switch position.
When the OPTIONS key is pressed, the following
message will first be displayed for 3 seconds:
Eight (8) Option Messages will then follow. Each will be
displayed for 3 seconds before the next display is
automatically indexed. When all messages are
displayed, the display message will automatically change
to show a chiller STATUS message, just as if the
STATUS key was pressed.
Refer to Table 1 for a list of the displays and the
corresponding switch positions in the order they appear.
Two possible messages may appear for each of the eight
messages depending on the Dip Switch position.
A detailed explanation of the meaning of each message
and a guide to programming the associated switch is
provided on page 80.
Fig. 22 shows the location and verification of switch
positioning of S1.
OPERATING HRS.
START COUNTER
H R S
1 =
1 4 3 , 2
=
3 8 2
S T R
1 =
1 1 7 , 2
=
1 1 2
OPTIONS
T H E
F O L L O W I N G
A R E
P R O G R A M M E D
DISPLAY/
SWITCH “OPEN” MESSAGE
SWITCH “CLOSED” MESSAGE
SWITCH
1
2
3
4
5
6
7
8
R E F R I G E R A N T
T Y P E
R 1 3 4 A
R E F R I G E R A N T
T Y P E
R 2 2
M A N U A L
L E A D
/
L A G
A U T O M A T I C
L E A D
/
L A G
A C R O S S - T H E - L I N E
M O T O R
S T A R T I N G
W Y E
D E L T A
M O T O R
S T A R T I N G
E N G L I S H
U N I T S
R E A D O U T
S I
U N I T S
R E A D O U T
T H E R M A L
E X P A N S I O N
V A L V E S
T H E R M A L
E X P A N S I O N
V A L V E S
L O C A L
C O N T R O L
M O D E
R E M O T E
C O N T R O L
M O D E
S T A N D A R D
A M B I E N T
L O W
A M B I E N T
C O N T R O L
W A T E R
C O O L I N G
B R I N E
C O O L I N G
TABLE 1 – SWITCH POSITION AND DISPLAY
Содержание Millennium YCAS 316
Страница 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Страница 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Страница 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Страница 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Страница 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Страница 54: ...54 YORK INTERNATIONAL FIG 9 SYSTEM WIRING YCAS 140 246 CONNECTION DIAGRAM SYSTEM WIRING LD01466 D...
Страница 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Страница 60: ...60 YORK INTERNATIONAL FIG 12 CONNECTION DIAGRAM WYE DELTA YCAS 140 246 CONNECTION DIAGRAM WYE DELTA LD01458 D...
Страница 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Страница 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Страница 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...