72
YORK INTERNATIONAL
UNIT CONTROLS AND OPERATION
INTRODUCTION
The YORK Millennium Computer Control Center is a
microprocessor based control system capable of multi-
circuit control to maintain chilled liquid temperature and
provide safety control.
A 40 character display (2 lines of 20 characters) allows the
operator to display system operating parameters as well
as access programmed information already in memory. A
keypad for programming and accessing setpoints,
pressures, temperatures, motor current, cutouts, daily
schedule, options, and fault information is provided.
A master switch is available to activate or de-activate the
chiller system. Separate system (SYS) switches for each
refrigerant system (up to 4) are provided on the
Microprocessor Board.
Remote cycling, current limiting, and chilled water
temperature reset can be accomplished by user supplied
dry contacts.
Compressor starting, stopping, loading and unloading
decisions are performed by the Microprocessor to
maintain leaving water temperatures. These decisions
are a function of temperature deviation from setpoint and
the rate of change of temperature.
MICROPROCESSOR BOARD
The Microprocessor Board is the controller and decision
maker in the control panel. System inputs from pressure
transducers and temperature sensors are connected
directly to the Microprocessor Board. Other inputs from
the I/O Expansion Board such as slide valve position, oil
temperature, etc. are multiplexed on the Expansion Board
and are also sent to the Microprocessor Board. The
Microprocessor Board circuitry multiplexes all of these
analog inputs, digitizes them, and constantly scans them
to keep a constant watch on chiller operating conditions.
From this information, the Microprocessor then issues
commands to the Relay Output Board to activate and de-
activate contactors, solenoids, etc. for chilled liquid
control and safety control.
FIG. 18 – Millennium CONTROL CENTER
28164A
Содержание Millennium YCAS 316
Страница 11: ...FORM 201 10 NM1 11 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS English LD01444 LD01446...
Страница 13: ...FORM 201 10 NM1 13 YORK INTERNATIONAL YCAS 140 246 DIMENSIONS SI LD01440 LD01442...
Страница 15: ...FORM 201 10 NM1 15 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS English LD01454 LD01454...
Страница 17: ...FORM 201 10 NM1 17 YORK INTERNATIONAL YCAS 216X 266X DIMENSIONS SI LD01450 LD01448...
Страница 33: ...FORM 201 10 NM1 33 YORK INTERNATIONAL 28514A FILTER DRYER LIQUID STOP VALVE...
Страница 37: ...FORM 201 10 NM1 37 YORK INTERNATIONAL LD01285 FIG 3 SCREW CHILLER REFIGERANT FLOW DIAGRAM...
Страница 54: ...54 YORK INTERNATIONAL FIG 9 SYSTEM WIRING YCAS 140 246 CONNECTION DIAGRAM SYSTEM WIRING LD01466 D...
Страница 59: ...FORM 201 10 NM1 59 YORK INTERNATIONAL FIG 11 CONTINUED LD01465 D...
Страница 60: ...60 YORK INTERNATIONAL FIG 12 CONNECTION DIAGRAM WYE DELTA YCAS 140 246 CONNECTION DIAGRAM WYE DELTA LD01458 D...
Страница 61: ...FORM 201 10 NM1 61 YORK INTERNATIONAL FIG 12 CONTINUED LD01458 D...
Страница 69: ...FORM 201 10 NM1 69 YORK INTERNATIONAL FIG 16 CONTINUED LD01206 D...
Страница 71: ...FORM 201 10 NM1 71 YORK INTERNATIONAL FIG 17 CONTINUED LD01202 D...