3 COMPRESSOR
CONDENSER FAN CONTROL
The chiller is equipped with 12 or 14 condenser fans,
with 4 or 5 fans per system as given below. Fan control
is via Outside Ambient Temperature (OAT) and Dis-
charge Pressure (DP). There are six stages of fan con-
trol utilizing 3 outputs per system. The fan stages will
operate according to Table 4 or Table 5 depending on
the number of fans/system. There will be a minimum 5
second delay between all fan stages.
Condenser fan ON conditions are governed solely by
the Discharge Pressure (DP). When the DP rises above
15.2 bar (220 PSIG), fan stage 1 is activated. From here,
subsequent fan stages are activated as the DP rises in
increments of 1.0 bar (15 PSIG), except stage 6, which
is activated when the DP rises over 2.0 bar (290 PSIG).
The system will remain at the highest fan stage reached
unless the OFF conditions given in the next paragraph
are satisfied.
Condenser fan OFF conditions are governed by both
the DP and OAT. Fan staging will be decreased from
the highest stage reached if both the DP and OAT re-
quirements are met. For example, if a system is at a fan
stage of 4, and the DP falls under 13.4 bar (195 PSIG)
and the OAT drops below 23.9°C (75°F), the fan stage
will be reduced to 3. The ON/OFF conditions are pro-
vided in the next two tables.
The tables below also indicate fan contactors, wire num-
bers, and Relay Output Board or I/O Expansion Board
Output numbers relating to fans energized. SYS 1 fan
contactors are controlled by Relay Output Board # 1.
SYS 2 by Relay Output Board # 2. SYS 3 is controlled
by I/O Expansion Board #2.
FIG. 67– CONDENSER FAN CONTROL LAYOUT FOR DXST COMPRESSORS UNITS
LD05022
%
(Not present on 60 Hz Models.)
8
Содержание Millennium YCAS 0693
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7...