32
YORK INTERNATIONAL
The size of any pipework attached to a relief valve must
be of sufficient diameter so as not to cause resistance
to the operation of the valve. Unless otherwise speci-
fied by local regulations, table internal diameter depends
on the length of pipe required and is given by the fol-
lowing formula:
D
5
= 1.447 x L
Where:
D = minimum pipe internal diameter
L = length of pipe in meters
If relief pipework is common to more than one valve
its cross sectional area must be at least the total required
by each valve. Valve types should not be mixed on a
common pipe. Precautions should be taken to ensure
that the outlet of relief valves/vent pipe remain clear of
obstructions at all times.
DUCTWORK CONNECTION
General Requirements
The following ductwork recommendations are intended
to ensure satisfactory operation of the unit. Failure to
follow these recommendations could cause damage to
the unit, or loss of performance, and may invalidate the
warranty.
When ducting is to be fitted to the fan discharge it is
recommended that the duct should be the same cross
sectional area as the fan outlet and straight for at least 1
meter (three feet) to obtain static regain from the fan.
Ductwork should be suspended with flexible hangers
to prevent noise and vibration being transmitted to the
structure. A flexible joint is also recommended between
the duct attached to the fan and the next section for the
same reason. Flexible connectors should not be allowed
to concertina.
The unit is not designed to take structural loading. No
significant amount of weight should be allowed to rest
on the fan outlet flange, deck assemblies or condenser
coil module. No more than 1 meter (3 feet) of light con-
struction ductwork should be supported by the unit.
Where cross winds may occur, any ductwork must be
supported to prevent side loading on the unit.
If the ducts from two or more fans are to be combined
into a common duct, back-flow dampers should be fit-
ted in the individual fan ducts. This will prevent recir-
culation of air when only one of the fans is running.
Units are supplied with outlet guards for safety and to
prevent damage to the fan blades. If these guards are
removed to fit ductwork, adequate alternative precau-
CONNECTION TYPES & SIZES
For connection sizes relevant to individual models re-
fer to the Technical Data Section.
COOLER CONNECTIONS
Standard chilled liquid connections on all coolers are
of the Victaulic Groove type.
Option Flanges
One of two types of flanges may be fitted depending on
the customer or local Pressure Vessel Code require-
ments. These are Victaulic-Adapter flanges, normally
supplied loose, or weld flanges which may be supplied
loose or ready fitted. Victaulic-Adapter and weld flange
dimensions are to ISO 7005 - NP10.
REFRIGERANT RELIEF VALVE PIPING
Coolers and oil separators are each protected against
internal refrigerant overpressure by refrigerant relief
valves. For coolers, a pressure relief valve is mounted
on each of the main refrigerant lines connecting the
cooler to the compressors. On oil separators the pres-
sure relief valve is mounted on the side near top of the
vessel body.
It is recommended that a piece of pipe is fitted to each
valve and directed so that when the valve is activated
the release of high pressure gas and liquid cannot be a
danger or cause injury. For indoor installations pres-
sure relief valves should be piped to the exterior of the
building.
Weld Flange
Victaulic Adapter
LD03523
FIG. 7 – FLANGE ATTACHMENTS
LD03521
FIG. 6 – VICTAULIC GROOVE
Installation
Содержание Millennium YCAS 0693
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7...