132
YORK INTERNATIONAL
1.8
TRANSFORMERS
3 Transformers (2T, 3T, and 4T) are located in the Con-
trol Panel. These transformers convert the 115VAC
Control Power Input to 24VAC to operate the micro-
processor circuitry.
1T: Supplies 24V to I/O Expansion Board # 2
2T: This 75VA transformer supplies the
microprocessor power supply.
3T: Supplies the I/O Expansion Board # 1 voltage
for slide valve control.
4T: Supplies power to the Motor Protector
Modules.
1.9
MOTOR PROTECTOR MODULES
A Motor Protector Module for each compressor is lo-
cated in the Control Panel. These modules supply mo-
tor over-temperature protection, 3-phase current pro-
tection, phase imbalance, phase rotation, and a program-
ming and troubleshooting 7 segment display.
The motor over-temperature protection is supplied by
3 temperature sensors imbedded in the motor wind-
ings 120 degrees apart. The module monitors these
sensors allowing it to sense a hot winding and shut
down the compressor if motor cooling is inadequate.
The on-board C.T.s provide 3-phase current protec-
tion which look at 3 of the 6 motor legs and send
an analog signal proportional to average motor cur-
rent to I/O Expansion board and on to the micropro-
cessor board for microprocessor low/high current pro-
tection and current display. This allows the micro to
monitor current and shut a system down if low or high
motor current is sensed. This is a non-adjustable pro-
tection circuit electronically sized to a system's motor
specifications.
Internally, the on-board 3 C.T.s and internal circuitry
allow the Motor Protector Module to protect against
high motor current as programmed on the Motor Pro-
tector dip switches. These switches are set at the fac-
tory according to motor specifications.
The module also provides phase rotation protection to
assure the screw compressor does not rotate backwards
A single-phase protection circuit located in the module
also monitors for a phase imbalance. If current imbal-
ance exceeds 17% of the average motor current in one
of the phases, the Motor Protector will recognize it and
shut the system down.
Whenever the Motor Protector Module senses a fault,
internal contacts will open and shut the system down.
These contacts are wired in series with the compressor
motor contactor. When the contact opens, the micro will
attempt to start the system 2 more times. Since the motor
contactor signal path from the Relay Output Board to
the motor contactor is broken by the Motor Protector
Module contacts, it will lock the system out after 3
faults. The Motor Protector Module must then be reset
by removing 115VAC power from the Control Panel.
After the Motor Protector is reset, the individual sys-
tem SYS switch must be switched OFF and then ON to
reset the microprocessor to allow restart of the system.
Anytime the module faults, a thorough
investigation of the problem should be
performed before attempting to return
the system to operation. Failure to per-
form this investigation could lead to
motor or compressor failure. Addi-
tional details on the Motor Protector
Module can be found on page 16.
MicroPanel Contents
Содержание Millennium YCAS 0693
Страница 36: ...36 YORK INTERNATIONAL FIG 8 POWER PANEL SECTION CONT D OPTIONS PANEL LAYOUT TYPICAL 00246VIP Installation...
Страница 49: ...49 YORK INTERNATIONAL FORM 201 18 NM4 7 This page intentionally left blank...
Страница 65: ...65 YORK INTERNATIONAL FORM 201 18 NM4 LD04179 7...
Страница 79: ...79 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 83: ...83 YORK INTERNATIONAL FORM 201 18 NM4 This page intentionally left blank 7...
Страница 87: ...87 YORK INTERNATIONAL FORM 201 18 NM4 LD04268 7...
Страница 119: ...119 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 57 COMPRESSOR COMPONENTS LD03669 7...
Страница 120: ...120 YORK INTERNATIONAL COMPRESSOR COMPONENTS CONT D FIG 58 COMPRESSOR COMPONENTS LD03670 Technical Data...
Страница 121: ...121 YORK INTERNATIONAL FORM 201 18 NM4 COMPRESSOR COMPONENTS CONT D FIG 59 COMPRESSOR COMPONENTS LD03671 7...