York G8C Series Скачать руководство пользователя страница 9

035-15241-003 Rev. A (201)

Unitary Products Group

9

2.

If two duct systems are used as could be the case with a 
coil-blower or a self-contained A/C unit, the furnace and 
A/C unit should be controlled by a single combination 
heating and cooling thermostat which will prevent the fur-
nace and A/C unit from operating simultaneously.  

RETURN AIR AND FILTERS

RETURN AIR TEMPERATURE

This furnace design is to be operated in normal household
temperatures. The continuous return air temperature must
not be below 60°F or above 85°F.

RETURN AIR CONNECTION - UPFLOW

The return air may be brought in through the bottom of the
furnace or through one or both sides of the furnace casing.
The furnace casing may be cut out so that side return air con-
nections may be used. The furnace is supplied with flanges
on the top of the furnace to which the return air duct may be
fastened. The casing top is embossed to indicate where to
bend the flanges. If a side return is to be used, cut out the
side of the casing 14" high by 16 1/4" wide using the lances in
the casing side as a guide. 

DO NOT CUT THE OPENING

LARGER THAN 14"x 16 1/4".

 It is not permissible to cut out

the back of the furnace.

The return air ducts to the furnace must have a total cross
sectional area of not less than two square inches per 1000
BTUH of furnace input rating for heating operation. If air con-
ditioning is to be installed with the furnace, or if it may be
added at a later time, larger return air ducts may be required,
depending on the capacity of the air conditioner and the air-
flow required. For applications requiring more than 1800
CFM, it will be necessary to use the bottom return, both side
returns or one side plus the bottom return.

RETURN AIR CONNECTION - DOWNFLOW
(50-125 MBH MODELS ONLY)

The return air connection to the furnace must be attached to
the top of the furnace. It is not permissible to cut out the side
of the furnace casing for side return ducts. The furnace is
supplied with flanges on the top of the furnace to which the
return air duct may be fastened. The casing top is embossed
to indicate where to bend the flanges.

The return air ducts to the furnace must have a total cross
sectional area of not less than two square inches per 1000
BTUH of furnace input rating for heating operation. If air con-
ditioning is to be installed with the furnace, or if it may be
added at a later time, larger return air ducts may be required,
depending on the capacity of the air conditioner and the air-
flow required. The return air opening in the top of the furnace
is large enough for the largest capacity air conditioner for
which the furnace blower is rated.

RETURN AIR CONNECTION - HORIZONTAL

The return air duct must be connected to the inlet end of the
furnace. It is not permissible to cut out the side of the furnace
casing for side return ducts. The furnace is supplied with
flanges on both ends of the furnace to which the supply and
return air ducts may be fastened. The casing is embossed on
both ends to indicate where to bend the flanges.

The return air ducts to the furnace must have a total cross
sectional area of not less than two square inches per 1000
BTUH of furnace input rating for heating operation. If air con-
ditioning is to be installed with the furnace, or if it may be
added at a later time, larger return air ducts may be required,
depending on the capacity of the air conditioner and the air-
flow required. The return air opening in the top of the furnace
is large enough for the largest capacity air conditioner for
which the furnace blower is rated.

FILTERS

Air filters must be used with this furnace. Failure to do so will
cause dirt to accumulate on the furnace blower motor, blower
wheel, heat exchanger and air conditioning coil, resulting in
reduced system efficiency, erratic control performance and
possible equipment damage.

Air velocity must not exceed 300 feet per minute through low
velocity disposable filters. Air velocity must not exceed 650
feet per minute through high velocity cleanable permanent fil-
ters. Use of a filter that is too small will cause static pressure
in the duct system to be too high, which will have an adverse
effect on heating and cooling operation.

If a separate heating and separate cooling ther-
mostat is used, a manually operated electrical in-
terlock switch must be installed to prevent
simultaneous operation of both systems and to
avoid a possible hazardous condition due to
overheating of the conditioned space.

When side return air ducts are used, a solid metal
block-off panel must be used to block the bottom
opening in the furnace. Failure to do so could
cause flue gases to be drawn into the living
space, which could result in asphyxiation.

When the furnace is installed so that supply ducts
carry air circulated by the furnace to areas out-
side the space containing the furnace, the return
air must also be handled by a duct(s) sealed to
the furnace casing and terminating outside the
space containing the furnace. Failure to do so
can result in asphyxiation.

Содержание G8C Series

Страница 1: ...OSITION 50 125 MBH Models 4 INSTALLATION POSITION 150 MBH Models 4 CONVERSION INFORMATION 50 125 MBH Models 4 TO CONVERT FROM DOWNFLOW TO UPFLOW CONFIGURATION 50 125 MBH Models 4 TO CONVERT FROM UPFLO...

Страница 2: ...aning compounds plastic items or con tainers gasoline kerosene cigarette lighter fluid dry cleaning fluids or other volatile fluid 3 Paint thinners and other painting com pounds 4 Paper bags boxes or...

Страница 3: ...000 60 000 1200 17 1 2 10 x 8 35 65 165 1 3 4 1FB0318 75 000 60 000 1600 21 10 x 10 30 60 160 1 2 4 1FB0319 100 000 80 000 1600 21 10 x 10 40 70 170 1 2 4 1FB0319 100 000 80 000 2000 24 1 2 2 10 x 6...

Страница 4: ...conversion instructions starting on Page 5 and Page 6 INSTALLATION POSITION 150 MBH Models This furnace may be installed in an upflow or horizontal poi sion No conversion is necessary CONVERSION INFO...

Страница 5: ...ion on the vent blower using the three screws supplied on the vent blower See Figure 4 10 Rotate the vent blower 180 so that its outlet points toward the inlet air end of the furnace See Figure 3 11 L...

Страница 6: ...to any combustible mate rials must be maintained These required minimum clear ances are shown below and on a label in the furnace Minimum Clearances Upflow Front 2 inches Back 0 inches Sides 0 inches...

Страница 7: ...the furnace If all air is from inside building the total free area of each opening must be at least one square inch for each 1 000 BTUH of furnace input but not less than 100 square inches If all air...

Страница 8: ...ply air duct attached to the furnace be provided with a removable access panel The opening should be accessible when the furnace is installed in service and should be large enough that smoke or reflec...

Страница 9: ...uired depending on the capacity of the air conditioner and the air flow required The return air opening in the top of the furnace is large enough for the largest capacity air conditioner for which the...

Страница 10: ...ecifics It is recommended that a gas cock shutoff valve be installed in the gas supply line outside the casing where it is readily accessible as close to the furnace as is practicable as shown in Figu...

Страница 11: ...ALVE PRESSURE SWITCH VENT VENT PIPE TRANSITION GAS PIPE 3 DIAMETER VENT PIPE GAS SHUT OFF VALVE ROLL OUT SWITCH DIRT LEG VENT BLOWER FURNACE CONTROL FIGURE 10 UPFLOW CONFIGURATION 50 125 MBH MODELS ON...

Страница 12: ...n the limits shown FIGURE 11 UPFLOW HORIZONTAL 150 MBH MODEL ONLY BLOWER DOOR SWITCH ROLL OUT SWITCHES BURNERS HOT SURFACE IGNITOR GAS VALVE PRESSURE SWITCH GAS PIPE GAS SHUT OFF VALVE ROLL OUT SWITCH...

Страница 13: ...nd fastened to the furnace flue collar using screws where required 9 Joints in the vent pipe must be securely made and any horizontal run of the vent pipe must be supported less than one support every...

Страница 14: ...rtical portion of the chimney or vent above the connector A vent connector must not pass through any ceiling floor firewall or fire partition A single wall metal pipe vent connec tor must not pass thr...

Страница 15: ...a device that keeps the power venter in operation for a short period at the end of each burner cycle in order to clear out all flue gases from the vent Manufacturers of power ven ters also can supply...

Страница 16: ...he furnace The furnace control board has a ter minal marked TWIN which can be used to cause two furnace blowers to operate together If two furnaces are to be twinned using a single wall thermo stat co...

Страница 17: ...TAP EXTERNAL STATIC PRESSURE INCHES W C 0 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 50 40 1200 75 60 1200 HIGH 1407 1367 1315 1279 1211 1138 1053 961 MED 1141 1130 1092 1059 1009 945 876 782 LOW 885 894 8...

Страница 18: ...r shorted wires bad pressure switch Three flashes Pressure switch failed to close Check vent blower pressure switch vent blockage disconnected pres sure hose Four flashes Limit switch open Check for o...

Страница 19: ...mally open pressure switch contacts 3 As the vent blower increases in speed the contacts of the pressure switch will close and complete the electrical circuit to the ignitor 4 During the next 30 secon...

Страница 20: ...not reach your gas supplier call the fire department 3 USE ONLY YOUR HAND TO MOVE THE GAS CON TROL LEVER OR SWITCH NEVER USE TOOLS IF THE LEVER OR SWITCH WILL NOT MOVE BY HAND DON T TRY TO REPAIR IT...

Страница 21: ...t is necessary to achieve the correct input rate use the following formula GAS VALUE X 3600 DESIRED INPUT SECONDS NEEDED Example 1000 BTU gas furnace input 100 000 BTUH Seconds for one cubic foot 1000...

Страница 22: ...g of the heat exchanger and flue gas pas sageways is not necessary and is not recommended under normal circumstances REPLACEMENT PARTS Should it be necessary to replace any component parts these may b...

Страница 23: ...Ignitor Bracket 15 Gas Orifice 16 Door Switch 17 Capacitor 18 Blower Wheel 19 Blower Motor 20 Sensor Rod 21 Blower Motor Clamp 22 Rubber Motor Mounts 23 Transition 24 Rollout Switch Bracket 25 Door La...

Страница 24: ...hout notice Printed in U S A 035 15241 003 Rev A 201 Copyright by York International Corp 2001 All rights reserved Supersedes 035 15241 002 Rev A 800 Unitary 5005 Norman Products York OK Group Drive 7...

Отзывы: