background image

661693-UIM-E-1212

Johnson Controls Unitary Products

7

SECTION IV: ELECTRIC HEATER 

INSTALLATION

If the air handler requires electric heat, install the electric heat kit
according to the installation instructions included with the kit. After
installing the kit, mark the air handler nameplate to designate the heater
kit that was installed. If no heater is installed, mark the name plate
appropriately to indicate that no heat kit is installed.

Use only 6HK heater kits, as listed on Air Handler name plate and in
these instructions. Use data from Tables 4 through 9 for information on
required minimum motor speed tap to be used for heating operation,
maximum over-current protection device required and minimum electri-
cal supply wiring size required – for listed combination of Air Handler
and Heater Kit.

SECTION V: LINE POWER CONNECTIONS

Power may be brought into the unit through the supply air end of the
unit (top when unit is vertical) or the left side panel. Use the hole appro-
priate to the unit’s orientation in each installation to bring conduit from
the disconnect. The power lead conduit should be terminated at the
electrical control box. Refer to Tables 6 throught 9 to determine proper
wire sizing. Also see Figure 2. To minimize air leakage, seal the wiring
entry point at the outside of the unit.

All electrical connections to air handlers must be made with copper con-
ductors. 

Direct connection of aluminum wiring to air handlers is

not approved.

If aluminum conductors are present, all applicable local and national
codes must be followed when converting from aluminum to copper con-
ductors prior to connection to the air handler.

If wire other than uncoated (non-plated), 75° C ambient, copper wire is
used, consult applicable tables of the National Electric Code (ANSI/
NFPA 70). The chosen conductor and connections all must meet or
exceed the amperage rating of the overcurrent protector (circuit breaker
or fuse) in the circuit.

Additionally, existing aluminum wire within the structure must be sized
correctly for the application according to National Electric Code and
local codes. Caution must be used when sizing aluminum rather than
copper conductors, as aluminum conductors are rated for less current
than copper conductors of the same size.

 FIGURE 12:  

Blower Delay Control Board

AHR/PSC CONTROL BOARD

 FIGURE 13:  

Line Power Connections

*1'

*1'
/8*

FIELD POWER WIRING

(208/230-1-60)

-803(5%$5

NO ELECTRIC HEAT

COMPONENT CODES

GND

GROUND LUG

CB

CIRCUIT BREAKER

CKT - CIRCUIT

CN

WIRE CONNECTOR/NUT

32:(5
6833/<

CKT 1

1 PHASE ELECTRIC HEAT OPTIONS:
SINGLE SOURCE POWER

MULTI-SOURCE POWER

MULTI-SOURCE POWER

WITH JUMPER BAR

TERMINAL BLOCK OR

CIRCUIT BREAKER

POWER

SUPPLY

POWER

SUPPLY

3 PHASE ELECTRIC HEAT POWER OPTIONS:
SINGLE SOURCE POWER

MULTI-SOURCE POWER

2 CIRCUITS ON13KW-20KW

3 CIRCUITS ON 25KW

TERMINAL BLOCK OR

CIRCUIT BREAKER

CKT 2

CKT 1

POWER

SUPPLY

CB

CB

CB

CB

CB

2 CIRCUITS ON13KW-20KW

3 CIRCUITS ON 25KW

POWER

SUPPLY

*1'

*1'

*1'

*1'

POWER

SUPPLY

L1

L2

L1

L2

L1

L2

CKT 2

CKT 3

L1

L2

L1

L2

CN

CN

CB

CB

CB

L1

L2

L3

L1

L2

L3

L1

L2

L3

Содержание 41HP AHR18B

Страница 1: ......

Страница 2: ...ervice personnel can perform basic maintenance functions such as cleaning and replacing the air filters When work ing on heating cooling equipment observe precautions in the man uals and on the labels...

Страница 3: ...secondary drain It should be piped to a loca tion that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 5 When an evaporat...

Страница 4: ...ort bracket See Figure 5 This positions the deflector below the feeder tubes to channel the condensate to the drain pan DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These f...

Страница 5: ...is recommended a block off plate approximately 8 in height and running the full width of the ple num be attached to the supply opening Please refer to Figure 8 as a visual aid The use of this block o...

Страница 6: ...ed and piped to a location that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped The drain pan connections are designed to...

Страница 7: ...um wiring to air handlers is not approved If aluminum conductors are present all applicable local and national codes must be followed when converting from aluminum to copper con ductors prior to conne...

Страница 8: ...require ments Read and heed all unit caution labels It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump Standard wiring will only bring on the first s...

Страница 9: ...4 11 5 32 0 39 2 3 1 3 8 9 4 11 5 6HK 1 2 6501506 14 4 10 8 13 2 36 9 45 1 3 6 4 4 10 8 13 2 6HK 1 2 6501806 17 3 13 0 15 9 44 3 54 2 6 5 7 9 13 0 15 9 6HK 1 2 6502006 19 2 14 4 17 6 49 2 60 2 7 2 8...

Страница 10: ...and local codes TABLE 6 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 1 60 Continued Air Handler Models Heater Models1 2 Heater Amps 240V Field Wiring Min Circuit Ampacity MOP 3 Min Wire Siz...

Страница 11: ...L DATA FOR MULTI SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Ci...

Страница 12: ...t AHR18B3XH21 High 1145 1100 1055 1005 930 845 725 Medium 755 750 725 665 605 485 435 Low 680 655 625 585 540 395 300 AHR24B3XH21 High 1305 1285 1225 1175 920 915 835 Medium 930 920 890 845 705 760 50...

Страница 13: ...661693 UIM E 1212 Johnson Controls Unitary Products 13 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram PSC Single Phase Heat Kits...

Страница 14: ...NT CODES GND EQUIPMENT GROUND FL FUSIBLE LINK HE HEATING ELEMENT LS LIMIT SWITCH REL RELAY FIELD POWER WIRING 208 230V FACTORY WIRING 208 230V FACTORY WIRING LOW VOLTAGE L1 L2 L3 L1 L2 L3 GND GND GND...

Страница 15: ...661693 UIM E 1212 Johnson Controls Unitary Products 15 SECTION XI TYPICAL THERMOSTAT CONNECTIONS FIGURE 17 Typical Wiring Diagram PSC...

Страница 16: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Страница 17: ...he thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat noting and correcting any problems Operate the unit through emergency heating cy...

Страница 18: ...o change without notice Published in U S A 661693 UIM E 1212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 661693 UIM D 1012 York International Corp 5005 York Drive Norman OK 7...

Отзывы: