background image

661693-UIM-E-1212

4

Johnson Controls Unitary Products

HORIZONTAL CONVERSION

These air handler units are supplied ready to be installed in a upflow
and right hand horizontal position. If unit requires left hand positioning,
the unit must have the coil assembly repositioned.

1.

Remove blower, coil, and filter access panels.

For horizontal left installations, follow steps 2 - 8.
2.

Remove tubing connection panel.

3.

Slide coil assembly out of air handler.

4.

Rotate cabinet 180º so blower outlet is facing down.

5.

Re-install coil assembly on coil support bracket.

6.

Re-attach tubing connection panel.

7.

For horizontal applications, rotate air handler 90º into desired orien-
tation.

8.

Re-position drain plugs as necessary based on air handler orienta-
tion.

9.

Re-position and replace access panels.

SUCTION FEEDER TUBECONDENSATE DEFLECTOR

UPFLOW

No action required. See Figure 4.

HORIZONTAL LEFT OR RIGHT

Use an appropriate tool to pry out water deflector with two or three s-
clips from the vertical drain pan, see Figure 4. Relocate the deflector
with s-clips on the Horizontal Drain Pan lined up to the coil support
bracket. See Figure 5. This positions the deflector below the feeder
tubes to channel the condensate to the drain pan.

DUCT FLANGES

Four flanges are provided to attach ductwork to the furnace. These
flanges are rotated down for shipment. In order to use the flanges,
remove the screw holding an individual flange, rotate the flange so it is
in the upward position and reinstall the screw then repeat this for all 4
flanges. See Figure 7.

If the flanges are not used, they must remain in the rotated down posi-
tion as shipped.

 FIGURE 3:  

Typical Installation

For both horizontal applications, the condensate deflector should be
positioned as shown in Figure 2.

Conversion must be made before brazing the refrigerant connections
to the coil.

 FIGURE 4:  

Condensate Deflector on Vertical Drain Pan

UPFLOW

HORIZONTAL RIGHT

HORIZONTAL LEFT

HEAT

HEA

T

HEA

T

NOTICE

NOTICE

CONDENSATE

DEFLECTOR

S-CLIPS (3)

VERTICAL

DRAIN PAN

The condensate deflector should be installed in the s-clip section
which is inside the drain pan edge. See Figure 6.

 FIGURE 5:  

Condensate Deflector on Horizontal Drain Pan Edge

 FIGURE 6:  

S-Clip Installation

 FIGURE 7:  

Duct Attachment

NOTICE

S-CLIPS ON HORIZONTAL PAN

FEEDER

TUBES

CONDENSATE

DEFLECTOR

CONDENSATE

DEFLECTOR

S-CLIP

DRAIN PAN

WALL

FACTORY
INSTALLED

FOR DUCT ATTACHMENT,
IF NEEDED

Содержание 41HP AHR18B

Страница 1: ......

Страница 2: ...ervice personnel can perform basic maintenance functions such as cleaning and replacing the air filters When work ing on heating cooling equipment observe precautions in the man uals and on the labels...

Страница 3: ...secondary drain It should be piped to a loca tion that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped 5 When an evaporat...

Страница 4: ...ort bracket See Figure 5 This positions the deflector below the feeder tubes to channel the condensate to the drain pan DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These f...

Страница 5: ...is recommended a block off plate approximately 8 in height and running the full width of the ple num be attached to the supply opening Please refer to Figure 8 as a visual aid The use of this block o...

Страница 6: ...ed and piped to a location that will give the occupant a visual warning that the primary drain is clogged If the secondary drain is not used it must be capped The drain pan connections are designed to...

Страница 7: ...um wiring to air handlers is not approved If aluminum conductors are present all applicable local and national codes must be followed when converting from aluminum to copper con ductors prior to conne...

Страница 8: ...require ments Read and heed all unit caution labels It is possible to vary the amount of electric heat turned on during the defrost cycle of a heat pump Standard wiring will only bring on the first s...

Страница 9: ...4 11 5 32 0 39 2 3 1 3 8 9 4 11 5 6HK 1 2 6501506 14 4 10 8 13 2 36 9 45 1 3 6 4 4 10 8 13 2 6HK 1 2 6501806 17 3 13 0 15 9 44 3 54 2 6 5 7 9 13 0 15 9 6HK 1 2 6502006 19 2 14 4 17 6 49 2 60 2 7 2 8...

Страница 10: ...and local codes TABLE 6 ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY 208 230 1 60 Continued Air Handler Models Heater Models1 2 Heater Amps 240V Field Wiring Min Circuit Ampacity MOP 3 Min Wire Siz...

Страница 11: ...L DATA FOR MULTI SOURCE POWER SUPPLY 208 230 3 60 Air Handler Models Heater Models Total Heater Amps 240V Min Circuit Ampacity MOP1 Min Wire Size AWG 2 208V 230V 208V 230V 208V 230V Circuit Circuit Ci...

Страница 12: ...t AHR18B3XH21 High 1145 1100 1055 1005 930 845 725 Medium 755 750 725 665 605 485 435 Low 680 655 625 585 540 395 300 AHR24B3XH21 High 1305 1285 1225 1175 920 915 835 Medium 930 920 890 845 705 760 50...

Страница 13: ...661693 UIM E 1212 Johnson Controls Unitary Products 13 SECTION X WIRING DIAGRAM FIGURE 15 Wiring Diagram PSC Single Phase Heat Kits...

Страница 14: ...NT CODES GND EQUIPMENT GROUND FL FUSIBLE LINK HE HEATING ELEMENT LS LIMIT SWITCH REL RELAY FIELD POWER WIRING 208 230V FACTORY WIRING 208 230V FACTORY WIRING LOW VOLTAGE L1 L2 L3 L1 L2 L3 GND GND GND...

Страница 15: ...661693 UIM E 1212 Johnson Controls Unitary Products 15 SECTION XI TYPICAL THERMOSTAT CONNECTIONS FIGURE 17 Typical Wiring Diagram PSC...

Страница 16: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply a...

Страница 17: ...he thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat noting and correcting any problems Operate the unit through emergency heating cy...

Страница 18: ...o change without notice Published in U S A 661693 UIM E 1212 Copyright 2012 by Johnson Controls Inc All rights reserved Supersedes 661693 UIM D 1012 York International Corp 5005 York Drive Norman OK 7...

Отзывы: