5188238-YIM-D-0518
6
Johnson Controls Ducted Systems
Figure 1: XN036-060 Component Location
Location
Use the following guidelines to select a suitable location for
these units:
1.
Unit is designed for
outdoor installation only
.
2.
Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.
Suitable for mounting on roof curb.
4.
For ground level installation, use a level concrete slab with
a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rails.
Do not tie slab to the building foundation.
5.
Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.
Maintain level tolerance to 1/2” across the entire width and
length of unit.
Economizer
Hood
Electric Heat
Accessory Location
High Efficiency
Compressor
Highly Efficient
Enhanced Copper
Tube/Enhanced
Aluminum Fin
Or
Micro-Channel
Aluminum
Tube/Aluminum
Fin Condenser
Full Perimeter Baserails
With Forklift Slots And
Lifting Holes
Smart Equipment™
Control Board
Belt Drive Or
Direct Drive
Blower
Knockout
For Side
Control Entry
GFCI
Convenience Outlet
3/4” PVC Female
Condensate Drain
Smoke
Detector
Slide-In
Economizer
Knockout
For Side
Power Entry
HACR
Breaker
Table 1: XN036-060 Unit Limitations
Size
(Tons)
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
036
(3.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
048
(4.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
060
(5.0)
208/230-1-60
187
252
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125